AUMA ACE C 01.2 Profinet Series Manual page 28

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Description of the data interface
Table 23: Byte 27: Out of specification 3
Bit
Designation
(process representation)
0
Wrn FO cable budget
1
Wrn FOC
2
Wrn input AIN 2
3
Wrn input AIN 1
4
Internal warning
5
Wrn op.mode starts
6
Wrn op.mode run time
7
Op. time warning
Table 24: Byte 28: Out of specification 4
Bit
Designation
(process representation)
0
1
2
Wrn setpoint position
3
PVST required
4
Wrn FOC connection
5
Failure behav. active
6
PVST abort
7
PVST fault
28
Byte 27: Out of specification 3
Prm-Text-Def GSD file
Warning FO Cable budget
Warning FOC
Warning input AIN 2"
Warning input AIN 1"
Internal warning
Warning On time Starts
Warning On time Running
Operation time warning
Byte 28: Out of specification 4
Prm-Text-Def GSD file
Warning setpoint position
PVST required
Warning FOC connection
Failure behaviour active
PVST abort
PVST fault
Byte 29: Function check 1
Causes of the Function check signal in accordance with NAMUR recommendation
NE 107.
Value
Description
1
Reserved for future FO cable variant
0
No signal
1
Reserved for future FO cable variant
0
No signal
1
Warning: Loss of signal analogue input 2
0
No signal
1
Warning: Loss of signal analogue input 1
0
No signal
1
Collective signal 15: Internal warning
0
No internal warning
1
Warning: Max. number of motor starts (starts) exceeded
0
No signal
1
Warning: Max. running time/h exceeded
0
No signal
1
Warning: Max. permissible operating time for an operation
(OPEN-CLOSE) exceeded
0
No signal
Value
Description
No signal (reserved)
No signal (reserved)
1
Warning: Loss of signal of actuator setpoint position
0
No signal
1
Warning: A Partial Valve Stroke Test (PVST) should be
performed.
0
1
Reserved for future FO cable variant
0
No signal
1
The failure behaviour is active.
0
No signal
1
Partial Valve Stroke Test (PVST) was aborted or could
not be started. Remedy: Perform RESET or restart PVST.
0
No signal
1
Partial Valve Stroke Test (PVST) could not be successfully
completed.
0
No signal
Actuator controls
AC 01.2/ACExC 01.2 Profinet