AUMA ACE C 01.2 Profinet Series Manual page 55

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
ID
Type
Parameters
PRM
4407
enum
Interlock source
Table 62: Customer settings > PVST
ID
Type
Parameters
Data length = 18 bytes
PRM
4288
enum
PVST operation mode
PRM
4195
enum
PVST behaviour
PRM
4193
U16
PVST stroke
PRM
4194
MMSS01
PVST monitoring
PRM
4287
MMSS01
PVST operating time
PRM
4286
MMSS01
PVST reversing time
PRM
4292
enum
PVST reminder
PRM
4289
U16
PVST reminder period
PRM
4944
enum
PVST source
Table 63: Device configuration > Local controls
ID
Type
Parameters
Data length = 22 bytes
PRM
160
enum
Indication light 1 (left)
PRM
557
enum
Indication light 2
PRM
561
enum
Indication light 3
PRM
565
enum
Indication light 4
PRM
569
enum
Indicat. light 5 (right)
Ac-
Default
Setting value
cess
R/W
3
1 : Interface
2 : Fieldbus
3 : Active comm. source
Ac-
Default
Setting value
cess
R/W
0
0: Stroke
1: End position test
R/W
1
0: OPEN
1: CLOSE
R/W
100
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
R/W
600
Min = 10 [0.1 s]
Max = 3000 [0.1 s]
R/W
20
Min = 1 [0.1 s]
Max = 600 [0.1 s]
R/W
20
Min = 1 [0.1 s]
Max = 600 [0.1 s]
R/W
0
0: Function not active
1: Function active
R/W
0
Min = 0
Max = 65535
R/W
0
0: Active interface
1: I/O interface
2: Fieldbus interface
Access
Default
Setting value
R/W
370
R/W
269
R/W
270
R/W
268
R/W
369
Appendix
Explanation
Source of interlock function
Explanation
Setting the operation mode
PVST: Stroke = stroke-con-
trolled PVST; based on travel
across a defined stroke (stroke
PVST) within a given time
(PVST monitoring time); can be
started in any valve position
(even outside the end position)
End position test = PVST based
on test when leaving the end
position within a defined time
(PVST travel time); Can only be
started from an end position
PVST (Partial Valve Stroke
Test) behaviour
PVST (Partial Valve Stroke
Test) stroke
PVST (Partial Valve Stroke
Test) monitoring time
PVST (Partial Valve Stroke
Test) operating time
Waiting time during PVST prior
to returning to initial position.
When function is active, a mes-
sage is generated if no PVST
can be executed during remind-
er period.
Reminder period of PVST func-
tion. Generates message if no
PVST was executed during this
reminder period.
Source for PVST command
Explanation
Signal assignment for indication
light 1 (left) on the local controls
Signal assignment for indication
light 2 on the local controls
Signal assignment for indication
light 3 on the local controls
Signal assignment for indication
light 4 on the local controls
Signal assignment for indication
light 5 (right) on the local con-
trols
55