AUMA ACE C 01.2 Profinet Series Manual page 49

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
ID
Type
Parameters
PRM
3693
enum
Priority REMOTE
PRM
3694
enum
Fieldbus auto enable
Table 51: Customer settings > I/O interface
ID
Type
Parameters
Data length = 4 bytes
PRM
519
enum
Self-retaining Remote
PRM
533
enum
Self-retaining Remote
II
Table 52: Customer settings > Positioner
ID
Type
Parameters
Data length = 30 bytes
PRM
84
enum
Adaptive behaviour
PRM
87
U16
Outer dead band
PRM
86
U16
Dead time
PRM
2012
U16
Dead band OPEN
PRM
213
U16
Dead band CLOSE
PRM
2916
U16
Posit. hyst. OPEN
PRM
2917
U16
Posit. hyst. CLOSE
PRM
5316
U16
Dead band min. (ad.2)
PRM
5317
U16
Dead band max. (ad.2)
PRM
215
I32
Tolerance CLOSE
PRM
214
I32
Tolerance OPEN
PRM
4167
enum
Limit setting range
Access
Default
Setting value
R/W
0
0: Selector switch Local
1: Sel. sw. Local + Off
R/W
1
0: Off
1: On
Ac-
Default
Setting value
cess
R/W
3
0: Off (push-to-run op.)
1: OPEN
2: CLOSE
3: OPEN and CLOSE
4: OPEN & CL w/o STOP
R/W
0
0: Off (push-to-run op.)
1: OPEN
2: CLOSE
3: OPEN and CLOSE
4: OPEN & CL w/o STOP
Ac-
Default
Setting value
cess
R/W
0
0: Off
1: Adaptive I
R/W
10
Min = 1 [0.1 %]
Max = 100 [0.1 %]
R/W
5
Min = 2 [0.1 s]
Max = 600 [0.1 s]
R/W
5
Min = 0 [0.1 %]
Max = 100 [0.1 %]
R/W
5
Min = 0 [0.1 %]
Max = 100 [0.1 %]
R/W
5
Min = 0 [0.1 %]
Max = 50 [0.1 %]
R/W
5
Min = 0 [0.1 %]
Max = 50 [0.1 %]
R/W
2
Min = 2 [0.1 %]
Max = 50 [0.1 %]
R/W
25
Min = 2 [0.1 %]
Max = 50 [0.1 %]
R/W
0
Min = 0 [0.1 %]
Max = 50 [0.1 %]
R/W
1000
Min = 950 [0.1 %]
Max = 1000 [0.1 %]
R/W
0
0: Function not active
1: Function active
Appendix
Explanation
Preserving the operation mode
REMOTE in selector switch po-
sition LOCAL or OFF depending
on the enable signal
Automatic generation of enable
signal for priority REMOTE
function in case loss of fieldbus
communication
Explanation
Setting the operation behaviour
(push-to-run operation or self-
retaining) for binary operation
commands (OPEN, STOP,
CLOSE) from remote.
Setting the self-retaining Re-
mote II mode
Explanation
Setting the adaptive behaviour
of the positioner
Setting the outer dead band (ir-
relevant for adaptive behaviour)
Setting the dead time
Setting dead band OPEN (irrel-
evant for adaptive behaviour)
Setting dead band CLOSE (irrel-
evant for adaptive behaviour)
Hysteresis in direction OPEN
(for adaptive positioner only)
Hysteresis in direction CLOSE
(for adaptive positioner only)
Minimum dead band Xt (adapt-
ive positioner 2)
Maximum dead band Xt (adapt-
ive positioner 2)
Tolerance for the function
"Closing fully" for end position
CLOSED
Tolerance for the function
"Opening fully" for end position
OPEN
Function Limit setting range
49