AUMA ACE C 01.2 Profinet Series Manual page 51

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
ID
Type
Parameters
PRM
1872
U16
Fail.pos.OPEN CLOSE
PRM
4809
U16
Failure position MPV
Table 55: Customer settings > EMCY behaviour
ID
Type
Parameters
Data length = 26 bytes
PRM
68
enum
EMCY fail.reac.
PRM
67
enum
EMCY operation mode
PRM
2924
enum
EMCY source
PRM
230
enum
EMCY operation
PRM
4808
U16
EMCY position MPV
PRM
231
U16
EMCY position
PRM
70
enum
By-pass torque
PRM
69
enum
Thermal by-pass
PRM
71
enum
By-pass timer
PRM
2950
enum
By-pass operat.profile
PRM
3255
enum
By-pass Interlock
Ac-
Default
Setting value
cess
R/W
500
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
R/W
500
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
Ac-
Default
Setting value
cess
R/W
1
1: Good signal first
2: Immediately active
R/W
0
0: Remote only
1: Remote and local
R/W
3
1: I/O interface
2: Fieldbus interface
3: I/O or fieldbus
4: Active interface
R/W
0
0: STOP
1: CLOSE
2: OPEN
3: Approach EMCY pos.
R/W
10
Min = 0 [0.1 s]
Max = 1800 [0.1 s]
R/W
0
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
R/W
0
0: Off
1: On
R/W
0
0: Off
1: On
R/W
0
0: Off
1: On
R/W
0
0: Off
1: On
R/W
0
0: Off
1: On
Appendix
Explanation
Failure position for OPEN-
CLOSE duty
Failure position of multiport
valve
Explanation
EMERGENCY failure reaction.
The EMERGENCY failure reac-
tion defines the actuator beha-
viour once the EMERGENCY
signal is initiated.
Determines the availability of
EMERGENCY behaviour de-
pending on the selector switch
position Local or Remote
Source for EMERGENCY beha-
viour
Actuator reaction in EMER-
GENCY operation mode
EMERGENCY position of multi-
port valve
Setting the EMERGENCY posi-
tion
By-passing the torque monitor-
ing in EMERGENCY operation
mode
By-passing the thermal monitor-
ing in EMERGENCY operation
mode
By-passing the timer function in
EMERGENCY operation mode
By-pass of operation profile in
EMERGENCY operation mode
By-pass of interlock function in
operation mode EMERGENCY