AUMA ACE C 01.2 Profinet Series Manual page 24

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Description of the data interface
Bit
Designation
(process representation)
6
Config. error REMOTE
7
Incorrect phase seq
Table 15: Byte 17: Warnings 1
Bit
Designation
(process representation)
0
1
2
3
FQM fail safe fault
4
Torque wrn CLOSE
5
Torque wrn OPEN
1)
6
SIL fault
7
Wrn no reaction
1)
The safety function indications via communication interface are for information only and must not be used as part of a safety function.
The digital I/O signals of the SIL module must be used for this purpose.
Table 16: Byte 18: Warnings 2
Bit
Designation
(process representation)
0
Wrn controls temp.
1
2
3
24 V DC external
4
5
RTC voltage
24
Prm-Text-Def GSD file
Configuration error RE-
MOTE
Incorrect phase sequence
Byte 17: Warnings 1
The warning signals are for information only and do not interrupt or disable an
operation (as opposed to faults).
Prm-Text-Def GSD file
Torque Warning CLOSE
Torque Warning OPEN
SIL fault
Warning no reaction
Byte 18: Warnings 2
Prm-Text-Def GSD file
Warning controls temperat-
ure
24 V DC, external
RTC button cell
Value
Description
1
Config. error of REMOTE interface active.
0
No signal
1
The phase conductors L1, L2 and L3 are connected in
the wrong sequence.
0
Phase sequence is ok.
Value
Description
No signal (reserved)
No signal (reserved)
No signal (reserved)
FQM Fail Safe fault active:
- "FQM FS-Ready" not ready although "FQM FS-Esd-
Active" not active
- "FQM FS-Ready" ready although "FQM FS-Esd-Active"
active
- "FQM-Timeout-Tension" active
- "FQM-Timeout-Limit" active
1
Warning: Limit value for torque warning in direction
CLOSE exceeded.
0
No signal
1
Warning: Limit value for torque warning in direction OPEN
exceeded.
0
No signal
1
Warning: A SIL fault of the SIL sub-assembly has oc-
curred.
0
No signal
1
Warning: No actuator reaction to operation commands
within the set reaction time.
0
No signal
Value
Description
1
Warning: Temperature within actuator controls housing
too high.
0
No signal
No signal (reserved)
No signal (reserved)
1
The external 24 V DC voltage supply of the controls has
exceeded the power supply limits.
0
No signal
No signal (reserved)
1
Warning: Voltage of RTC button cell too low.
0
No signal
Actuator controls
AC 01.2/ACExC 01.2 Profinet