AUMA ACE C 01.2 Profinet Series Manual page 17

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
4.1.2.
Description of the bytes in the process representation input
Table 5: Byte 1: Logic signals
Bit
Designation
(process representation)
0
End position OPEN
1
End position CLOSED
Byte 1: Logic signals
Bits 3, 6, and 7 are collective signals.
Bits 5 and 4 of the logical signals (byte1) indicate a logical operation of the actuator,
i.e. they are set when the actuator has received the command to perform an electrical
operation (also active when e.g. the actuator is in a stepping pause during stepping
mode or waiting for the end of the dead time).
Prm-Text-Def GSD file
End position OPEN
End position CLOSED
Value
Description
1
For limit seating: Limit switch operated in direction OPEN
For torque seating: Torque switch and limit switch oper-
ated in direction OPEN
0
No signal
1
For limit seating: Limit switch operated in direction
CLOSE
For torque seating: Torque switch and limit switch oper-
ated in direction CLOSE
0
No signal
Description of the data interface
17