Table 80: Diagnostic > Profinet > Communication status
ID
Type
Parameters
Data length = 26 bytes
PZD
657
BOOL
Channel 1 DataEx
PZD
613
BOOL
Channel 1 activity
PZD
614
BOOL
Channel 2 activity
PZD
1663
BS16
Network status
PZD
1664
enum
Module status
PZD
1365
BOOL
Fieldbus mod. not
avail.
Table 81: Diagnostic > Profinet > I&M 0
ID
Type
Parameters
Data length = 74 bytes
PRM
5175
U16
Vendor ID
PZD
1750
S20
Profinet order no.
PRM
1762
S20
Serial no. controls
PRM
5155
U16
I&M0 hardw. revision
PRM
5209
S20
I&M0 softw. revision
PRM
4948
U16
Prm Revision Counter
PRM
5178
U16
I&M0 profile ID
PRM
5179
U16
I&M0 profile spec.type
PRM
5180
U16
I&M0 version
PRM
5181
U16
I&M0 supported
64
Ac-
Default
Setting value
cess
R
R
R
R
0: Global link status
1: IP Address Established
2: Reserved
3: Link Status Port 1
4: Link Status Port 2
R
0: Setup
1: Network Init
2: Wait Process
3: Idle I/O
4: Process Active I/O
5: Error
7: Exception
R
Ac-
Default
Setting value
cess
R
R
R
R
R
R
R
R
R
R
Actuator controls
AC 01.2/ACExC 01.2 Profinet
Explanation
Channel 1 is currently used to
exchange data (DataEx)
Activity of fieldbus available on
channel 1
Activity of fieldbus available on
channel 1
Min. one connection to network
available
IP address assigned
No signals
Network connection at port 1
available
Network connection at port 2
available
Initialisation of Profinet module
in progress
Network initialisation of Profinet
module in progress
Devices waiting for I/O connec-
tion to I/O controller
Connected I/O controller in
STOP mode or has not yet sent
valid data
Connection to an I/O controller
active and no valid data received
Configuration data is inconsist-
ent or starting parameters faulty
Serious error or unexpected be-
haviour of Profinet module or
Profinet application detected
The fieldbus module is not
available
Explanation
Manufacturer ID
Profinet order number
Serial number of controls
I&M0 hardware revision
I&M0 software revision
Parameter Revision Counter
I&M0 profile ID
I&M0 profile specification type
I&M0 version
I&M0 supported