Description of the data interface
Table 11: Byte 13: Not ready REMOTE 1
Bit
Designation
(process representation)
0
Wrong oper. cmd
1
Sel. sw. not REMOTE
2
Interlock active
3
Local STOP
4
EMCY stop active
5
EMCY behav. active
6
FailState fieldbus
7
I/O interface
Table 12: Byte 14: Not ready REMOTE 2
Bit
Designation
(process representation)
0
FQM active
1
FQM init.
1)
2
SIL function active
3
Disabled
4
Interlock by-pass
5
PVST active
22
Bytes 11 and 12 transmit the current torque of the actuator (only if an MWG is installed
in the actuator).
The value transmitted is the current torque in percent or per mil of the nominal actuator
torque.
The value is transmitted in per mil (value: 0
The value 1,000 corresponds to 127,0 % torque in direction OPEN.
The value 500 is the torque zero point.
The value 0 corresponds to 127,0 % torque in direction CLOSE.
Byte 13: Not ready REMOTE 1
Prm-Text-Def GSD file
Wrong operation command
Selector switch not RE-
MOTE
Interlock active
Local STOP
EMCY stop active
EMCY behavior active
Fail Safe fieldbus
I/O interface
Byte 14: Not ready REMOTE 2
Prm-Text-Def GSD file
SIL function active
Disabled
Interlock by-pass
PVST active
1,000).
Value
Description
1
Wrong operation command
Indicates that several operation commands were received
simultaneously via Profinet (e.g. Remote OPEN and Re-
mote CLOSE simultaneously or Remote CLOSE/Remote
OPEN and Remote SETPOINT simultaneously) or that
the max. value for a setpoint position has been exceeded
(setpoint position > 1,000).
0
Operation commands are ok.
1
Selector switch is in position Local control (LOCAL) or
0 (OFF).
0
Selector switch is in position Remote control (REMOTE).
1
Actuator is interlocked.
0
No signal
1
Push button STOP of local controls is operated.
0
No signal
1
Operation mode EMERGENCY stop is active (EMER-
GENCY stop button has been pressed).
0
EMERGENCY stop button not pressed (normal operation).
1
Operation mode EMERGENCY behaviour is active
(EMERGENCY signal was sent).
0
No signal
1
No valid communication via communication interface
(despite available connection).
0
Communication via communication interface is ok.
1
The actuator is controlled via the I/O interface (parallel).
0
The actuator is controlled via communication interface.
Value
Description
Fail safe unit operates to defined end position
Initialisation of the actuator-FQM-valve combination is
active
1
Safety function of the SIL sub-assembly is active.
0
No signal
1
Actuator is in operation mode Disabled.
0
No signal
1
Bypass of interlock function is active.
0
No signal
1
Partial Valve Stroke Test (PVST) is active.
0
No signal
Actuator controls
AC 01.2/ACExC 01.2 Profinet