AUMA ACE C 01.2 Profinet Series Manual page 67

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
ID
Type
Parameters
PRM
4761
I32
Min. temp. controls
PRM
4760
I32
Max. temp. MWG
PRM
4764
I32
Min. temp. MWG
PRM
5061
I32
Max. vibration
PRM
3484
I16
Reset operating data
Table 84: Asset Management > Event report
ID
Type
Parameters
Data length = 10 bytes
PRM
185
U16
File size event. rep.
PRM
186
U16
Save interval
PRM
187
U16
Buffer size
PRM
189
enum
System event filter
Ac-
Default
Setting value
cess
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R/W
Access
Default
Setting value
R
548
Min = 0
Max = 1024
R
50000
Min = 1000
Max = 65535
R
50
Min = 10
Max = 100
R
31
0: Commands
1: Parameterization
2: Enable processes
3: System events
4: Simulation
Appendix
Explanation
Minimum temperature of con-
trols
Maximum temperature of MWG
Minimum temperature of MWG
Maximum actuator vibration
Value = 1:Deleting operating
data
Explanation
File size = number of events to
be recorded x 56/1024 kBytes
Save interval for event data from
buffer
Max. number of events in the
buffer
The event filter for System
defines which system events are
to be recorded into the event
report.
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac 01.2 profinet

Table of Contents