Actuator controls
AC 01.2/ACExC 01.2 Profinet
ID
Type
Parameters
PZD
1032
U32
Inner dead b. OPEN
PZD
1033
U32
Inner dead b. CLOSE
Table 77: Diagnostic > Operation mode
ID
Type
Parameters
Data length = 8 bytes
PZD
488
U32
On time
PZD
489
U32
No. mot. starts/h
PRM
5241
BOOL
Incorrect dir. rotation
Table 78: Diagnostic > Process controller
ID
Type
Parameters
Data length = 8 bytes
PZD
963
U16
Process setpoint
PZD
964
U16
Actual process value
PZD
824
U32
Op. com. PID contr.
Table 79: Diagnostic > Profinet > Device identification
ID
Type
Parameters
Data length = 196 bytes
PRM
5175
U16
Vendor ID
PRM
3633
U16
Ident code
PRM
5154
S40
Vendor name
PZD
1749
S20
Profinet device type
PZD
1669
S40
Profinet dev. name
PRM
5176
OS4
IP address
PRM
5182
OS4
Subnet mask
PRM
5183
OS4
Gateway
PRM
5205
S20
MAC address module
PRM
5206
S20
MAC address port 1
PRM
5207
S20
MAC address port 2
PRM
5219
S20
FW version module
Ac-
Default
Setting value
cess
R
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
R
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
Ac-
Default
Setting value
cess
R
Min = 0
Max = 3600
R
Min = 0
Max = 3600
R
Min = 0
Max = 1
Ac-
Default
Setting value
cess
R
0 [0,1 %]
1000 [0,1 %]
R
0 [0,1 %]
1000 [0,1 %]
R
0
0
Ac-
Default
Setting value
cess
R
R
R
R
R
R
R
R
R
R
R
R
Appendix
Explanation
Inner dead b. OPEN
Inner dead b. CLOSE
Explanation
On time
Number of motor starts/h
Explanation
Process setpoint of PID control-
ler
Actual process value of PID
controller
Op. com. PID contr.
Explanation
Manufacturer ID
Ident code
Manufacturer name
Profinet device type
Profinet device name
IP address
Subnet mask
Gateway
MAC address of Profinet module
MAC address of Profinet port 1
MAC address of Profinet port 2
Firmware version Profinet mod-
ule