Commissioning
3.6.
I & M functions
14
Channel 1 DataEx describes, whether the device can correctly communicate using
one of the two ports and whether the Profinet data has been sent to the device. A
Profinet user relation to I/O controller or I/O supervisor is available.
The actuator controls support the I & M function according to PNO guideline 3.502.
With the term Identification & Maintenance (I & M) functions, the PROFIBUS User
Organisation (PNO) introduced a new functionality for all Profibus and Profinet devices
with acyclic communication channel that may prove very useful for plant operators.
The I & M functions define how certain device-describing data (according to name
plate) is to be uniformly stored in the Profinet devices. Engineering tools may then
read and interpret the data according to a code which can be accessed on the PNO
server.This provides uniform and powerful access to all important and current device
data. This is a significant requirement for Asset Management.
Part of the device-specific I & M information is the unambiguous (asset) identification
using a manufacturer ID (MANUFACTURER_ID, for AUMA actuators = 319), the
order number (ORDER_ID) of the actuator as well as the individual serial number
(SERIAL_NUMBER). Further data supplements the asset information.
Table 4:
Record
Content
I&M0
MANUFACTURER_ID
ORDER_ID
SERIAL_NUMBER
HARDWARE_REVI-
SION
SOFTWARE_REVI-
SION
REVI-
SION_COUNTER
PROFILE_ID
PROFILE_SPECIF-
IC_TYPE
IM_VERSION
IM_SUPPORTED
I&M1
TAG_FUNCTION
TAG_LOCATION
I&M2
INSTALLA-
TION_DATE
I&M3
DESCRIPTOR
I&M4
SIGNATURE
AC 01.2/ACExC 01.2 Profinet
Size
Description
2 bytes
PROFINET I/O Object (F6h), attribute #2
('Vendor ID/I&M Vendor ID')
20 bytes
PROFINET I/O Object (F6h), attribute #8
('I&M Order ID')
16 bytes
PROFINET I/O Object (F6h), attribute #9
('I&M Serial Number')
2 bytes
PROFINET I/O Object (F6h), attribute #10
('I&M Hardware revision')
4 bytes
PROFINET I/O Object (F6h), attribute #11
('I&M Software revision')
2 bytes
PROFINET I/O Object (F6h), attribute #12
('I&M Revision counter')
2 bytes
PROFINET I/O Object (F6h), attribute #13
('I&M Profile ID')
2 bytes
PROFINET I/O Object (F6h), attribute #14
('I&M Profile specific type')
2 bytes
0101h (Internal, constant value)
2 bytes
001Eh (Internal, constant value)
32 bytes
Default: All bytes set to blanks (' ')
22 bytes
Default: All bytes set to blanks (' ')
16 bytes
Default: All bytes set to blanks (' ')
54 bytes
Default: All bytes set to blanks (' ')
54 bytes
Default: All bytes set to zero (00h)