Description of the data interface
Bit
Designation
(process representation)
2
Setpoint pos.reached
3
Not ready REMOTE
4
Running OPEN
5
Running CLOSE
6
Warning
7
Fault
Table 6: Byte 2: Actuator signals
Bit
Designation
(process representation)
0
Thermal fault
1
Phase fault
2
Selector sw. REMOTE
3
Selector sw. LOCAL
18
Prm-Text-Def GSD file
Setpoint reached
Not ready REMOTE
Running OPEN
Running CLOSE
Warnings
Fault
Byte 2: Actuator signals
Prm-Text-Def GSD file
Thermal fault
Phase failure
Selector switch REMOTE
Selector switch LOCAL
Value
Description
1
The position setpoint is within max. error variable (outer
dead band). Is only signalled if Profinet consumer (con-
troller) has set the Fieldbus SETPOINT bit (process
representation output).
0
No signal
1
Collective signal 04:
Contains the result of a disjunction (OR-operation) of all
bits comprised in bytes 13 and 14 (Not ready REMOTE
1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
0
In bytes 13 and 14, no signals are active (all bits are set
to 0).
1
An operation command in direction OPEN is performed
via the communication interface: Fieldbus OPEN or
Fieldbus SETPOINT (process representation output).
This bit remains also set during operation pauses (e.g.
due to the dead time or the reversing prevention time).
0
No operation in direction OPEN is performed via the
communication interface.
1
An operation command in direction CLOSE is performed
via the communication interface: Fieldbus CLOSE or
Fieldbus SETPOINT (process representation output).
This bit remains also set during operation pauses (e.g.
due to the dead time or the reversing prevention time).
0
No operation in direction CLOSE is performed via the
communication interface.
1
Collective signal 02:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 17 to 20 (Warning 1 to Warning 4).
0
In bytes 17 and 20, no warnings are active (all bits are
set to 0).
1
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
0
In bytes 15 and 16, no faults are active (all bits are set
to 0).
Value
Description
1
Motor protection tripped.
0
No signal
1
When connecting to a 3-phase AC system and with
internal 24 V DC supply of the electronics: Phase 2
is missing.
When connecting to a 3-phase or 1-phase AC system
and with external 24 V DC supply of the electronics:
One of the phases L1, L2 or L3 is missing.
0
All phases are available.
1
Selector switch is in position REMOTE.
0
Selector switch is not in position REMOTE.
1
Selector switch is in position LOCAL.
0
Selector switch is not in position LOCAL.