AUMA ACE C 01.2 Profinet Series Manual page 34

Actuator controls device integration
Hide thumbs Also See for ACE C 01.2 Profinet Series:
Table of Contents

Advertisement

Description of the data interface
34
If the multiport valve function is active (option), the entire byte 6 is used for coding
of multiport valve operation commands. Up to 16 positions can either be approached
selecting the shortest travel, in clockwise direction (CW), or in counterclockwise
direction (CCW). Furthermore, the actuator can also be operated without any position
indications in clockwise or counterclockwise direction (CW or CCW).
Table 31: Operation commands via byte 6 for activated multiport valve function
Value
≙ Operation direction/posi-
tion
0x01
Position 1
0x02
Position 2
0x04
Position 3
0x08
Position 4
0x10
Position 5
0x20
Position 6
0x40
Position 7
0x80
Position 8
0x81
Position 9
0x82
Position 10
0x83
Position 11
0x84
Position 12
0x85
Position 13
0x86
Position 14
0x87
Position 15
0x88
Position 16
0x90
CW
0x91
CW Position 1
0x92
CW Position 2
0x93
CW Position 3
0x94
CW Position 4
0x95
CW Position 5
0x96
CW Position 6
0x97
CW Position 7
0x98
CW Position 8
0x99
CW Position 9
AC 01.2/ACExC 01.2 Profinet
Behaviour
Position 1 is approached selecting the shortest
travel
Position 2 is approached selecting the shortest
travel
Position 3 is approached selecting the shortest
travel
Position 4 is approached selecting the shortest
travel
Position 5 is approached selecting the shortest
travel
Position 6 is approached selecting the shortest
travel
Position 7 is approached selecting the shortest
travel
Position 8 is approached selecting the shortest
travel
Position 9 is approached selecting the shortest
travel
Position 10 is approached selecting the shortest
travel
Position 11 is approached selecting the shortest
travel
Position 12 is approached selecting the shortest
travel
Position 13 is approached selecting the shortest
travel
Position 14 is approached selecting the shortest
travel
Position 15 is approached selecting the shortest
travel
Position 16 is approached selecting the shortest
travel
Actuator operates in clockwise direction (without
stop at any position).
Position 1 is approached in clockwise direction
(CW).
Position 2 is approached in clockwise direction
(CW).
Position 3 is approached in clockwise direction
(CW).
Position 4 is approached in clockwise direction
(CW).
Position 5 is approached in clockwise direction
(CW).
Position 6 is approached in clockwise direction
(CW).
Position 7 is approached in clockwise direction
(CW).
Position 8 is approached in clockwise direction
(CW).
Position 9 is approached in clockwise direction
(CW).
Actuator controls

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac 01.2 profinet

Table of Contents