This document contains information for installation, commissioning, operation and maintenance staff. It is intended to support device installation and commissioning. Reference documents: Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (refer to <Addresses>). Table of contents Page Safety instructions.........................
SQREx 14.2 with Ex plug/socket connector and screw-type terminals (KP, KPH) 14.2. Actuator controls AUMA MATIC AMExC 01.1 via Ex plug/socket connector with screw-type terminals (KP, KPH) 14.3. Actuator controls AUMA MATIC AMExC 01.1 via Ex plug/socket connector with terminal blocks (KES) Certificates..........................
To ensure safe device operation, the maintenance instructions included in this manual Maintenance must be observed. Any device modification requires prior consent of the manufacturer. 1.2. Range of application AUMA part-turn actuators are designed for the operation of industrial valves, e.g. butterfly valves and ball valves.
1, 2, 21, and 22. If temperatures >40 °C are to be expected at the valve mounting flange or the valve stem (e.g. due to hot media), please consult AUMA. Temperatures > 40 °C are not considered with regards to the non-electrical explosion protection.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Safety instructions Safety alert symbol warns of a potential personal injury hazard. The signal word (here: DANGER) indicates the level of hazard. 1.4. References and symbols The following references and symbols are used in these instructions: Information The term Information preceding the text indicates important notes and information.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Identification AMExC 01.1 Identification 2.1. Name plate Each device component (actuator, controls, motor) is equipped with a name plate. Figure 1: Arrangement of name plates Actuator name plate Controls name plate Motor name plate Additional plate, e.g.
Page 9
Ex marking Type and size These instructions apply to the following devices types and sizes: Part-turn actuators for open-close duty: SQEx 05.2, 07.2, 10.2, 12.2, 14.2 Part-turn actuators for modulating duty: SQREx 05.2, 07.2, 10.2, 12.2, 14.2 Ex marking Table 1: Marking for explosion protection (with example)
A part-turn actuator is an actuator which transmits a torque to the valve for less than one full revolution. It need not be capable of withstanding thrust. AUMA part-turn actuators are driven by an electric motor. A handwheel is provided for manual operation. Switching off in end positions may be either by limit or torque seating.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Transport, storage and packaging Transport, storage and packaging 3.1. Transport For transport to place of installation, use sturdy packaging. Hovering load! Risk of death or serious injury. Do NOT stand below hovering load.
SQREx 14.2 Assembly AMExC 01.1 Assembly 4.1. Mounting position AUMA actuators and actuator controls can be operated without restriction in any mounting position. 4.2. Handwheel fitting Information For transport purposes, handwheels from a diameter of 400 mm are supplied separ- ately.
Page 13
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Assembly Figure 7: Coupling fitting dimensions Coupling Valve shaft Grub screw Screw Table 3: Coupling fitting dimensions Type, size - output mounting flange X max [mm] Y max [mm] Z max [mm] SQEx/SQREx 05.2-F05...
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Assembly AMExC 01.1 Fasten actuator with screws [4]. Information: We recommend applying liquid thread sealing material to the screws to avoid contact corrosion. Fasten screws [4] crosswise with a torque according to table.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Assembly 4.4.1. Mounting positions: modify Flameproof enclosure, danger of explosion! Risk of death or serious injury. Before opening, ensure that there is no explosive gas and no voltage. Handle cover and housing parts with care.
The pertaining wiring diagram/terminal plan (in German and English language) is plan attached to the device in a weather-proof bag, together with these operation instructions. It can also be obtained from AUMA (state commission no., refer to name plate) or downloaded directly from the Internet (www.auma.com). Protection on site For short-circuit protection and for disconnecting the actuator from the mains, fuses and disconnect switches have to be provided by the customer.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Electrical connection Type of current, mains voltage and mains frequency must match the data on the Type of current, mains motor name plate. voltage and mains fre- quency Figure 10: Motor name plate (example)
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Electrical connection AMExC 01.1 Insert cable glands with Ex e approval and of size suitable for connection cables. The enclosure protection IP… stated on the name plate is only ensured if suit- able cable glands are used.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Electrical connection In case of a fault: Hazardous voltage while protective earth conductor is NOT connected! Risk of electric shock. Connect all protective earth conductors. Connect PE connection to external protective earth conductor of connecting cables.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Electrical connection AMExC 01.1 5.3.3. Terminal compartment: close Figure 16: Ex plug/socket connector: left KES, right KES flameproof Cover Screws for cover O-ring Terminal compartment: Type of protection Ex e Terminal compartment: Type of protection Ex d Frame Clean sealing faces of cover [1] and housing.
Versions with potentiometer in the actuator are not suitable. We recommend using an AUMA cable set "LSW". If the AUMA cable set is not used: Use suitable flexible and screened connecting cables. When using connecting cables, e.g. of the heater or switch, requiring direct...
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Electrical connection AMExC 01.1 Figure 19: Parking frame and Ex plug/socket connector with terminal blocks (KES) 5.4.3. Protection cover Protection cover for plug compartment when plug is removed. The open terminal compartment can be closed using a protective cover (not illustrated).
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Operation Operation 6.1. Manual operation For purposes of setting and commissioning, in case of motor or power failure, the actuator may be operated manually. Manual operation is engaged by an internal change-over mechanism.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Operation AMExC 01.1 Figure 21: Local controls Push button for operation command in direction OPEN Push button Stop Push button for operation command in direction CLOSE Selector switch Hot surfaces, e.g. possibly caused by high ambient temperatures or strong...
Page 27
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Operation Information For actuators equipped with positioner, it is possible to optionally select between open-close duty (REMOTE OPEN-CLOSE) and modulating duty (REMOTE SETPOINT). Selection is made via REMOTE MANUAL input, e.g. based on a 24 V DC signal (refer to wiring diagram).
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Indications AMExC 01.1 Indications 7.1. Indication lights Figure 22: Local controls with indication lights illuminated (default: green): End position OPEN reached illuminated (default: red): Collective fault signal illuminated (default: yellow): End position CLOSED reached...
Page 29
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Indications Figure 23: Mechanical position indicator Cover Indicator disc Mark Symbol for position OPEN Symbol for position CLOSED...
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Signals AMExC 01.1 Signals 8.1. Feedback signals via output contacts (binary) The output contacts can be used to indicate operation modes of the actuator or the controls as binary signals. The signals are assigned according to the order. Example:...
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning (basic settings) Commissioning (basic settings) Set selector switch to position 0 (OFF). Information: The selector switch is not a mains switch. When positioned to 0 (OFF), the actuator cannot be operated. The controls' power supply is maintained.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Commissioning (basic settings) AMExC 01.1 Exposed, rotating parts (discs/balls) at the valve! Pinching and damage by valve or actuator. End stops should be set by suitably qualified personnel only. Never completely remove the setting screws [2] and [4] to avoid grease leakage.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning (basic settings) If the valve end position is not reached: Slightly turn setting screw [4] counterclockwise until valve end position CLOSED can be safely set. Turning the setting screw [4] clockwise results in a smaller swing angle.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Commissioning (basic settings) AMExC 01.1 Turn handwheel by approximately half a turn (overrun) in the opposite direction. Press down and turn setting spindle [4] with screw driver in direction of the arrow and observe the pointer [5]: While a ratchet click is felt and heard, the pointer [5] moves 90°...
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning (basic settings) If you override the tripping point inadvertently (ratchet click is heard after the pointer has snapped): Continue turning the setting spindle in the same direction and repeat setting process.
"collective fault signal" on the local con- trols. Turn selector switch to position Reset. The fault signal is reset if the device is working properly. If no fault signal is initiated: Request AUMA service to check both wiring and selector switch. 9.8. Potentiometer setting —...
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning (basic settings) Figure 29: View of control unit Potentiometer Move valve to end position CLOSED. Turn potentiometer [1] clockwise to the stop. End position CLOSED corresponds to 0 % End position OPEN corresponds to 100 % Turn potentiometer [1] slightly in opposite direction.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Commissioning (basic settings) AMExC 01.1 Move valve to end position CLOSED. Connect ammeter for 0 20 mA to measuring points [4 and 5]. Turn potentiometer [1] clockwise to the stop. Turn potentiometer [1] slightly in opposite direction.
Page 41
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning (basic settings) Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert it correctly. Flameproof enclosure, danger of explosion! Risk of death or serious injury.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Commissioning controls settings AMExC 01.1 Commissioning controls settings The controls are set in the factory according to the order. The settings only have to be changed if the device is used for applications other than those specified in the order.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning controls settings The limit switching is set in such a way that the actuator switches off at the desired Limit seating switching points. The torque switching acts as overload protection for the valve.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Commissioning controls settings AMExC 01.1 Setpoint E1 [S1 7] DIP 3 and 5 10 V Table 11: Input range setting for actual value E2 Actual value E2 [S1 7] DIP 1...
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning controls settings Table 13: Further possible settings Behaviour on loss of signal of Signal type [S2 7] Setpoint E1 Actual value E2 DIP 1 2 3 4 Fail as is...
Page 48
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Commissioning controls settings AMExC 01.1 Connect lower setpoint to customer connection XK (terminals 2/3). The lower setpoint (0 V, 0 mA or 4 mA) is indicated on the label [5]. If the red LED [V10] E1/E2 <4 mA is illuminated: 4.1 Verify polarity of setpoint E1.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning controls settings 16. Adjust positioner using potentiometer max [P4]. 16.1 If both LEDs are OFF or the yellow LED [V27] is illuminated: Turn poten- tiometer max [P4] slightly counterclockwise until the green LED [V28] is illuminated.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Commissioning controls settings AMExC 01.1 Set dead time using potentiometer t-off [P10]: Dead time setting Reduce dead time: Turn potentiometer t-off [P10] counterclockwise. Increase dead time: Turn potentiometer t-off [P10] clockwise.
Page 51
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Commissioning controls settings Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert it correctly. Flameproof enclosure, danger of explosion! Risk of death or serious injury.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Corrective action Figure 41: Access to fuses Local controls Signal and control board Power supply unit Primary fuses on power supply unit F1/F2 G fuses F1/F2 AUMA Art. no.: Size 6.3 x 32 mm...
Page 54
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Corrective action AMExC 01.1 winding. The thermoswitch is tripped as soon as the max. permissible winding temperature has been reached. The actuator is stopped and the red indication light on the local controls is illuminated.
Only perform servicing and maintenance tasks when the device is switched off. AUMA AUMA offer extensive service such as servicing and maintenance as well as customer Service & Support product training. For the relevant contact addresses, please refer to <Addresses>...
Loosen the screws [2]. Remove plug/socket connector. Hereby, cover [1] and terminal board [5] or frame [6] remain together. Seal open plug/socket connection, e.g. using AUMA protection cover and parking frame. Fitting the plug: Clean sealing faces at the cover and the housing.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Servicing and maintenance Cable entries, cable glands, plugs etc. have to be checked for correct tightness and sealing. Consider torques according to manufacturer's details. If required, replace the components. Only use components which have an own EC type examination certificate.
The following technical data includes standard and optional features. For detailed information on the customer-specific version, refer to the order-relevant data sheet. This data sheet can be downloaded from the Internet at http://www.auma.com in German and English (indication of commission number required).
Page 59
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Technical data Electromechanical control unit Limit switching Counter gear mechanism for end positions CLOSED and OPEN Standard: Single switches (1 NC and 1 NO; not galvanically isolated) for each end position...
A1 Options: Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators) for AUMA power class B1 Auxiliary voltage output Standard: 24 V DC ±5 %, max. 50 mA for supply of the control inputs, galvanically isolated from internal...
Wiring diagram Refer to name plate The reversing contactors are designed for a lifetime of 2 million starts. For the assignment of AUMA power classes, please refer to electrical data on actuator. Not possible in combination with PTC tripping device 13.3.
Finish coating Powder coating Colour Standard: AUMA silver-grey (similar to RAL 7037) Lifetime AUMA part-turn actuators meet or even exceed the lifetime requirements of EN 15714-2. Detailed information can be provided on request. Weight Refer to separate technical data 13.4.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Spare parts Spare parts 14.1. Part-turn actuator SQEx 05.2 SQEx 14.2/SQREx 05.2 SQREx 14.2 with Ex plug/socket connector and screw-type terminals (KP, KPH)
Page 64
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Spare parts 14.2. Actuator controls AUMA MATIC AMExC 01.1 via Ex plug/socket connector with screw-type ter- minals (KP, KPH)
Page 66
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 AMExC 01.1 Spare parts 14.3. Actuator controls AUMA MATIC AMExC 01.1 via Ex plug/socket connector with terminal blocks (KES)
Page 68
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the representation.
IBEROPLAN S.A. AUMA Polska Sp. z o.o. ES 28027 Madrid PL 41-219 Sosnowiec Tel +34 91 3717130 Tel +48 32 783 52 00 AUMA Riester GmbH & Co. KG iberoplan@iberoplan.com biuro@auma.com.pl www.auma.com.pl Plant Müllheim AUMA Finland Oy DE 79373 Müllheim FI 02230 Espoo AUMA-LUSA Representative Office, Lda.