Actuator controls
AC 01.2/ACExC 01.2 Profinet
4.
Description of the data interface
4.1.
Input data (process representation input)
4.1.1.
Process representation input (default process representation)
Cyclic data
Configuration of cyclic data transfer is done via the Profinet controller only. Selection
of the input/channel or the respective input and/or output date is performed via the
slot/subslot configuration used to program a Profinet controller.
All I/O data is provided in slot 1, subslot 1. Data is structured in various blocks with
different properties. The following section comprises explanations about the different
blocks.
Process interface
Data structure is described on the basis of the automation system:
Input data: Is sent by the field device to the automation system
Output data: Is sent by the automation system to the field device
The consumer (controller) can read the state of the provider (actuator) via the process
representation input..
Grey bits are collective signals. They contain the results of a disjunction (OR
operation) of other information.
Module definition
Module ID="ID_MODULE_ADI_IN_0
ModuleIdentNumber="0x00008000"
ModuleInfo CategoryRef=Input
Name TextId="Inputs"
InfoText TextId="Prozessabbild Input Daten"
Sub-module definition
VirtualSubmoduleItem ID="ID_SUBMOD_ADI_PAIN_0"
SubmoduleIdentNumber="0x00002200"
API="0"
FixedInSubslots="1"
Name TextId="Inputs"
InfoText TextId="Prozessabbild Input Daten"
I/O data definition in sub-module
IOData IOPS_Length="1"
IOCS_Length="1"
Input Consistency="All items consistency">
Description of the data interface