Series - Fujitsu Airstage J-II Series Design & Technical Manual

Small vrf system
Table of Contents

Advertisement

2-1-2. V-II (230V) series
„ SETTINGS LIST
LED105
CODE
Setting Mode
No.
Pipe length
0
0
setting
Sequential start
1
0
shift
Cooling
1
1
capacity shift
Heating
1
2
capacity shift
1
3
Prohibited
Switching
between
2
0
batch stop or
emergency stop
*1: Do not set this for outdoor units with Slave setting.
LED104
Setting Function
CODE No.
Standard (131 to 213ft.)
0
0
(40 to 65m)
Short (less than 131ft.)
0
1
(less than 40m)
Medium (213 to 295ft.)
0
2
(65 to 90m)
Long 1 (295 to 394ft.)
0
3
(90 to 120m)
Long 2 (394 to 492ft.)
0
4
(120 to 150m)
0
0
Normal
0
1
21sec. Delay
0
2
42sec. Delay
0
3
63sec. Delay
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
4
Prohibited
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
0
Prohibited
0
1
Prohibited
0
0
Batch stop
0
1
Emergency stop
- (07 - 66) -
Outdoor unit
Factory
setting
Master Slave
l
Pipe length means the length
-
between master outdoor unit
¡
*1
and the nearest indoor unit.
The start-up timing of outdoor
l
unit (compressor) can be set
up so that it can delay several
seconds.
-
This feature is useful when
¡
*1
multiple number of outdoor units
are installed and turned on at
the same time
to limit the starting current.
l
-
¡
*1
l
-
¡
*1
l
Setting prohibited
This mode selects the pattern of
the stop function to be operated
by the external input terminal
(CN134).
l
•Batch stop: The stop of all
indoor units connected to same
refrigerant system due to input
signal coming from CN134.
-
•Emergency stop: When
¡
*1
emergency stop is actuated, the
indoor unit does not accept the
operation command from the
remote controller. On the other
hand, when the emergency
stop is released (no input from
CN134), the air conditioner
does not return to the original
operation until the indoor unit
is turned on by the remote
controller.
Remarks