z Example 2
- Individual connection
- Function setting for Fan setting when cooling thermostat OFF
Number 49-01 (Stop)
Forced thermostat off is one of the function to save energy. For example, case of using
ventilator at condition with outdoor temperature is lower than Indoor temperature, Indoor unit of
air conditioner stop based upon receiving signal from external controller. (Cooling Only)
Cooling operation
(Thermostat on)
●System figure example
External input wire
Except Indoor unit and
External wire (service
parts) all other items are
In d oo r unitとE xte rn a l Inp u t
field supplied.
W ire(S e rvice p arts)以外はすべ
て現地調達になります。
Direct digital
controller
Thermistor
Ventilator
Thermistor
Indoor
Outdoor
Temperature
Temperature
82˚F
88˚F
(28˚C)
(31˚C)
Office
Fri 10:00AM
Mode
Set Temp.
Fan
Custom
Cool
80°F
Auto
Auto
Heat
74°F
Cool
84°F
Room Temp.
Away
Heat
68°F
76°F
Vacation
Status
Menu
Relay
Indoor unit
Ventilator
- (08 - 21) -
Fan stop
(Thermostat off)
Indoor
Temperature
External controller
Indoor
thermistor
Indoor
Outdoor
Temperature
Temperature
88˚F
82˚F
(31˚C)
(28˚C)
Office
Fri 10:00AM
Mode
Set Temp.
Fan
Cool
80°F
Custom
Auto
Auto
74°F
Heat
Cool
84°F
Room Temp.
Away
Heat
68°F
76°F
Vacation
Status
Menu
Outdoor
Temperature
82˚F
75˚F
(28˚C)
(24˚C)
Office
Fri 10:00AM
Mode
Set Temp.
Fan
Custom
Cool
80°F
Auto
Auto
Heat
74°F
Cool
84°F
Room Temp.
Away
Heat
68°F
76°F
Vacation
Status
Menu
Outdoor
thermistor