Fujitsu Airstage J-II Series Design & Technical Manual page 565

Small vrf system
Table of Contents

Advertisement

1. SYSTEM DESIGN
1-1. REFRIGERANT SYSTEM
„ CONNECTABLE UNIT WITHIN 1 REFRIGERANT SYSTEM
Unit
Outdoor unit
Indoor unit
z Table
Capacity
Ton
(Btu/h)
3
36,000
4
48,000
5
60,000
z Caution
● When all indoor units are operating at maximum capacity, individual indoor unit operate at a
slightly lower capacity. (When connecting more than 100%)
● Do not exceed both of "connectable capacity range" and "maximum connectable indoor
unit", otherwise it may cause hinder the return of the refrigerant oil and cause a compressor
breakdown.
● Minimum connectable indoor unit number is 1.
Quantity
1 unit
1 to Max. 6 units
1 to Max. 8 units
1 to Max. 9 units
Outdoor unit
quantity
1
1
1
- (06 - 01) -
Remarks
3 ton (AOU36RLAVM)
4 ton (AOU48RLAVM)
5 ton (AOU60RLAVM)
Maximum
Connectable
connectable
capacity range
indoor unit
6
8
50% to 130%
9