7) When the number of indoor units appear on the LED104, LED105, press the SELECT button
(SW108), the display changes to volume ratio of the indoor units.
LED105
LED104
Ex.) When volume ratio of the indoor units is 120 %.
8) When "the number of indoor units" or "volume ratio of the indoor units connection" appears on
the LED104, LED105, press the ENTER button (SW109). When Indoor Unit Connection Check
is completed, the display changes to "PASS".
LED105
LED104
When Indoor Unit Connection Check is error, the display changes to "Err." or "number of error"
every one second.
LED105
LED104
Ex.) Shown numbers of error are three.
When confirm the contents of the error , push the ENTER button (SW109). When there are
some errors, display change by push the SELECT button (SW108).
●Number of indoor unit connection is error (5 Ton:1~9, 4 Ton:1~8, 3 Ton:1~6).
LED105
LED104
● Volume ratio of the indoor units connection is error (3, 4, 5 Ton:50~130%).
LED105
LED104
● Overlap address of the indoor unit is error.
LED105
LED104
Display the address of the overlap indoor unit, hold down the ENTER button (SW109).
LED105
LED104
Ex.) Shown that overlap address to indoor unit address 3.
9) To exit the Indoor Unit Connection Check , press the ENTER button (SW109) in the setting
completed status shown in step 8) above.
LED105
LED104
Next, press the MODE/EXIT button (SW107) to exit the Function mode.
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
- (07 - 57) -

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage aou36rlavmAirstage aou48rlavmAirstage aou60rlavmAirstage auua4tlav1Airstage auua7tlavAirstage auua9tlav ... Show all

Table of Contents