Vertical Air Handler Type - Fujitsu Airstage J-II Series Design & Technical Manual

Small vrf system
Table of Contents

Advertisement

1-8. VERTICAL AIR HANDLER TYPE

Model name
Power source
Available voltage range
Cooling
Capacity
Heating
Input power
Static pressure range
Standard static pressure
High
Airflow
Med
rate
Fan
Low
Type x Quantity
Motor output
High
Sound pressure
Med
level
Low
Length
Fin pitch
Rows x Stages
Heat exchanger
Face Area
Pipe type (Material)
Fin
Type (Material)
Type
Air filter (Locally
purchased)
Size
Material
Enclosure
Color
Net
Dimensions
(H x W x D)
Gross
Net
Weight
Gross
Liquid (Flare)
Connection
Gas (Flare)
pipe diameter
Drain hose
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB.
Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB.
Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit).
The protective function might work when using it outside the operation range.
ARUV12TLAV
1 Phase ~ 208/230V 60Hz
Btu/h
12,000
kW
3.5
Btu/h
13,500
kW
4.0
W
87
0.10 to 0.70
in.WG(Pa)
(25 to 175)
in.WG(Pa)
394 (670)
CFM
347 (590)
3
(m
/ h)
306 (520)
W
249
41
dB(A)
39
37
in. (mm)
FPI
(3 × 6) × 2
2
2
ft
. (m
)
1.5 (0.14)
Grooved H-pin (Copper)
16 × 22-1/4 × 1 (407 × 565 × 25.4)
painted galvanized steel
51 × 17-11/16 × 23-13/16 (1,295 × 450 × 605)
in. (mm)
58-1/2 × 24 × 30 (1,486 × 610 × 762)
139 (63)
lbs. (kg)
168 (77)
ø 1/4 (6.35)
in. (mm)
ø 1/2 (12.70)
- (04-12) -
ARUV18TLAV
ARUV24TLAV
187 to 253 V
18,000
24,000
5.3
7.0
20,000
27,000
5.9
7.9
142
233
0.10 to 0.80 (25 to 200)
0.50 (125)
630 (1,071)
862 (1,464)
547 (930)
800 (1,360)
506 (860)
689 (1,170)
Sirocco × 1
249
249
43
45
40
43
39
39
18 (457)
10
(2 × 12) × 2
(3 × 12) × 2
3.0 (0.28)
3.0 (0.28)
Slit (Aluminum)
MERV3
Gray
148 (67)
151 (69)
177 (81)
180 (82)
ø 3/8 (9.52)
ø 3/8 (9.52)
ø 5/8 (15.88)
ø 5/8 (15.88)
ø 3/4 (19.05) [I.D.]

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage aou36rlavmAirstage aou48rlavmAirstage aou60rlavmAirstage auua4tlav1Airstage auua7tlavAirstage auua9tlav ... Show all

Table of Contents