●Temperature conditions when the external heater is ON
Temperature (t) when the external heater is ON= Room temperature - set temperature
00
00
t ˂ -5.4°F (-3°C)
01
t ˂ -3.6°F (-2°C)
02
t ˂ -3.6°F (-2°C)
03
t ˂ -5.4°F (-3°C)
04
t ˂ -7.2°F (-4°C)
05
t ˂ -9.0°F (-5°C)
Set value of function: 61
01
02
- (07 - 115) -
03
04
t ≤ -0.9°F (-0.5°C)
t ≤ -1.8°F (-1°C)
t ≤ -3.6°F (-2°C)
t ≤ -5.4°F (-3°C)
t ≤ -7.2°F (-4°C)
t ≤ -9.0°F (-5°C)