Fujitsu Airstage J-II Series Design & Technical Manual page 725

Small vrf system
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Electricity meter
No. setting 1
7
0
*1
Electricity meter
No. setting 2
7
1
*1
Electricity meter
pulse setting 1
7
2
*2
Electricity meter
pulse setting 2
7
3
*2
9
0
Prohibited
*1: When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*2: When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
LED104
Setting Function
CODE No.
0
0
Setting number x00
0
1
Setting number x01
9
8
Setting number x98
9
9
Setting number x99
0
0
Setting number 0xx
0
1
Setting number 1xx
0
2
Setting number 2xx
0
0
Setting number xx00
0
1
Setting number xx01
9
8
Setting number xx98
9
9
Setting number xx99
0
0
Setting number 00xx
0
1
Setting number 01xx
9
8
Setting number 98xx
9
9
Setting number 99xx
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
4
Prohibited
0
5
Prohibited
0
6
Prohibited
0
7
Prohibited
0
8
Prohibited
0
9
Prohibited
1
0
Prohibited
1
1
Prohibited
- (07 - 78) -
Factory
Remarks
setting
l
Set the ones digit and tens digit of the No. of
the electricity meter connected to CN135.
l
Set the hundreds digit of the No. of the
electricity meter connected to CN135.
l
Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected to
CN135.
l
Set the hundreds digit and thousands digit of
the electricity meter pulse setting connected to
CN135.
l
Setting prohibited

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage aou36rlavmAirstage aou48rlavmAirstage aou60rlavmAirstage auua4tlav1Airstage auua7tlavAirstage auua9tlav ... Show all

Table of Contents