Fujitsu Airstage J-II Series Design & Technical Manual page 665

Small vrf system
Table of Contents

Advertisement

„ BUTTON NAME AND FUNCTION
● Refer to "1-2" for an outline of the address setting.
● It does not matter whether the refrigerant circuit address or indoor unit address is set first.
(The method shown here sets the indoor unit address first.)
● During address setting mode, indoor unit will not recognize any remote controller operation commands.
● NOTE: Address code display is as follows (operation lamp display)
MODE button
- Start the address setting mode
- Changes the address display digits
START/STOP button
Transmits address setting
TIMER set (-) button
Reconfirmation of address setting.
TIMER set (+) button
Confirmation of address setting.
IR RECEIVER UNIT
Indication of address code
Indication of address data number (the ten's place)
Indication of address data number (the one's place)
Long press ----- Switches between the address setting mode and
(3 sec more)
Short press ----- Switches the indicator display
OPERATION LAMP
OPERATION LAMP
TIMER LAMP
FILTER LAMP
MANUAL/AUTO button
the address setting complete mode.
INDOOR UNIT ADDRESS DISPLAY
ON
OFF
(Light continuously)
- (07 - 18) -
Function number
01 --- Indoor unit address
02 --- Refrigerant circuit address
Setting number
Setting number
* Indoor unit address valid range 00-63
Refrigerant circut address valid range 00-99
FAN button
Switches between the setting number (bottom line)
and function number (top line)
SET TEMP. " p " and " q " button
Increases and decreases the displayed number
MANUAL
REFRIGERANT CIRCUIT ADDRESS DISPLAY
ON
OFF
(Light 1 sec ON / 1 sec OFF)
AUTO