Fujitsu Airstage J-II Series Design & Technical Manual page 709

Small vrf system
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Switching
between
2
0
batch stop or
emergency stop
Snow falling
2
2
protection fan
mode
Interval setting
for snow falling
2
3
protection fan
mode
High static
2
4
pressure mode
2
5
Prohibited
2
6
Prohibited
2
7
Prohibited
Change of unit
2
8
(Temperature)
Change of unit
2
9
(Pressure)
*1: Do not set this for outdoor units with Slave setting.
LED104
Setting Function
CODE No.
0
0
Batch stop
0
1
Emergency stop
0
0
Enable
0
1
Disable
0
0
Standard (30minutes)
0
1
Short1 (5minutes)
0
2
Short2 (10minutes)
0
3
Short3 (20minutes)
0
0
Standard
High static pressure 1
0
1
(equivalent to 30Pa)
High static pressure 2
0
2
(equivalent to maximum)
0
3
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Celsius (°C)
0
1
Fahrenheit (°F)
0
0
MPa
0
1
psi
- (07 - 62) -
Outdoor unit
Factory
setting
Master Slave
This mode selects the pattern of
the stop function to be operated
by the external input terminal
(CN134).
l
•Batch stop: The stop of all
indoor units connected to same
refrigerant system due to input
signal coming from CN134.
-
¡
•Emergency stop: When
*1
emergency stop is actuated, the
indoor unit does not accept the
operation command from the
remote controller. On the other
hand, when the emergency
stop is released (no input from
CN134), the air conditioner
does not return to the original
operation until operate indoor
unit by the remote controller.
This mode operates the fans
l
of outdoor units in order to
-
prevent the units from stopping
¡
*1
operation when they are
covered by snow.
l
When the snow falling protection
-
fan mode is set, the operation
¡
*1
interval of the fans of outdoor
units can be selected.
When installing a duct to the
l
discharge of an outdoor unit, set
the high static pressure mode
according to the static pressure
of the duct to be installed.
¡
¡
Furthermore, use this setting if
the Airflow from the discharge
of an outdoor unit is poor, such
as when installed in a place with
a low ceiling.
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited
l
¡
¡
l
¡
¡
Remarks

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage aou36rlavmAirstage aou48rlavmAirstage aou60rlavmAirstage auua4tlav1Airstage auua7tlavAirstage auua9tlav ... Show all

Table of Contents