Fujitsu Airstage J-II Series Design & Technical Manual page 669

Small vrf system
Table of Contents

Advertisement

„ SETTING UP EACH INDOOR UNIT
01-01
01-02
„ RESET THE POWER AFTER SETTING UP ADDRESS OF ALL
INDOOR UNITS
Important
● If the reset is not performed, address cannot be read in normal operation.
● After all the addresses have been set, the circuit breaker needs to be switched off
for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
● The set address is stored in the PCB and will remain in memory even when the
power is turned off.
However, the address can be reset after power reset (if needed).
Record the address set in the indoor unit on a label, etc., and affix the label to the unit
so it can be used for after-sales service operations.
¾ Address 0 setting will not indicate TIMER LAMP and FILTER LAMP.
¾ Once the "RESET" button is pressed on the remote controller, the OPERATION MODE will be
set in the "AUTO MODE".
Adjust the OPERATION MODE to either "COOLING" or "HEATING" before trying to operate
the air conditioner.
¾ NOTE: If CUSTOM CODE is set to anything other than "A" ,the remote control must be set
accordingly to the .
01-03
Repeat steps (1) through to (25). Steps (1) through to (6)
and (21) to (25) only need to carried out if the custom
code is different to the factory setting of "A".
- (07 - 22) -