Fujitsu Airstage J-II Series Design & Technical Manual page 715

Small vrf system
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Change of unit
2
8
(Temperature)
Change of unit
2
9
(Pressure)
Energy saving
3
0
level setting
3
1
Prohibited
Capacity
priority setting
4
0
(in low noise
mode)
Low noise
4
1
mode setting
Low noise
mode
4
2
operation level
setting
Back up
6
0
operation
Electricity meter
No. setting 1
7
0
*2
Electricity meter
No. setting 2
7
1
*2"
*1: Do not set this for outdoor units with Slave setting.
*2: When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
LED104
Setting Function
CODE No.
0
0
Celsius (°C)
0
1
Fahrenheit (°F)
0
0
MPa
0
1
psi
0
0
Level 1 (stop)
Level 2 (operated at
0
1
40% capacity)
Level 3 (operated at
0
2
60% capacity)
Level 4 (operated at
0
3
80% capacity)
Level 5 (operated at
0
4
100% capacity)
0
0
Prohibited
0
1
Prohibited
0
0
Off (quiet priority)
0
1
On (capacity priority)
0
0
Off (Normal)
0
1
On (Low noise mode)
0
0
Level 1 (55dB)
0
1
Level 2 (50dB)
0
0
On
0
1
Off
0
0
Setting number x00
0
1
Setting number x01
9
8
Setting number x98
9
9
Setting number x99
0
0
Setting number 0xx
0
1
Setting number 1xx
0
2
Setting number 2xx
- (07 - 68) -
Outdoor unit
Factory
setting
Master Slave
l
¡
¡
l
¡
¡
l
The capacity limit can be
selected by the external
input terminal (CN133) when
operating with the "Energy
-
Saving Peak Cut function."
¡
*1
The lower the level, the more
the effect of energy saving, but
the cooling/heating performance
will also drop.
l
Setting prohibited
If the cooling/heating
performance becomes
insufficient when the low noise
l
mode is set, it is possible to
-
set "capacity priority" that
¡
*1
automatically cancels the low
noise mode (once performance
is restored, the mode will
automatically return to the low
noise mode).
l
-
¡
*1
The noise level when operating
l
-
in the low noise mode can be
¡
*1
set.
l
-
¡
*1
l
Set the ones digit and tens digit
of the No. of the electricity meter
¡
¡
connected to CN135.
l
Set the hundreds digit of the
No. of the electricity meter
¡
¡
connected to CN135.
Remarks