Fujitsu Airstage J-II Series Design & Technical Manual page 588

Small vrf system
Table of Contents

Advertisement

„ REFRIGERANT SYSTEM 2
b
(58.0Btu/h)
(44.0kBtu/h)
BP1
BP2
d
(21.5Btu/h)
b1
(14kBtu/h)
(12kBtu/h)
1
(14kBtu/h)
Indoor
unit
z System configuration
1
Model name
ARUL14
Capacity (Btu/h)
14,000
z System configuration
Outdoor unit 1
Model name
AOU48
Capacity (Btu/h)
48,000
z Capacity ratio
(Total indoor unit capacity) / (Total outdoor unit capacity)
= (58,000) / (48,000) = 120.8% (Within 50% to 130%)
z Selection of branch kit
Branch
Model
point No.
BP1
UTP-AX090A
BP2
UTP-AX090A
BP3
UTP-AX090A
HD1
UTR-H0906L
Outdoor
unit
a
BP3
c
(22.5kBtu/h)
e2
e1
(9.5kBtu/h)
2
3
(12kBtu/h)
(9.5kBtu/h)
Indoor
Indoor
unit
unit
(Indoor units)
2
3
ARUL12
ARUL09
ARUL07
12,000
9,500
7,500
(Outdoor unit)
- (06 - 24) -
Total cooling capacity of indoor units
connected downwards to the pipe.
f1
(7.5kBtu/h)
4
(7.5kBtu/h)
Indoor
unit
4
5
6
ARUL07
ARUL07
7,500
7,500
Model
UTP-AX090A
UTR-H0906L
HD1
f3
f2
(7.5kBtu/h)
(7.5kBtu/h)
5
6
(7.5kBtu/h)
(7.5kBtu/h)
Indoor
Indoor
unit
unit
Total Capacity
(Btu/h)
58,000
Q'ty
3
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage aou36rlavmAirstage aou48rlavmAirstage aou60rlavmAirstage auua4tlav1Airstage auua7tlavAirstage auua9tlav ... Show all

Table of Contents