EXAMPLE OF REFRIGERANT SYSTEM
z Example 1 (OK)
Outdoor unit
Model
Outdoor unit
AOU60R
Indoor unit 1
AUUB24
Indoor unit 2
AUUB18
z Example 2 (OK)
Outdoor unit
Model
Outdoor unit
AOU60R
Indoor unit 1
AUUB30
Indoor unit 2
AUUB24
Indoor unit 3
AUUB18
z Example 3 (Prohibited)
Outdoor unit
Model
Outdoor unit
AOU60R
Indoor unit 1
AUUB36
Indoor unit 2
AUUB36
Indoor unit 3
AUUB36
Indoor unit 1
Indoor unit 2
Total
Connectable indoor
Capacity
capacity
(Btu/h)
(Btu/h)
60,000
60,000
24,000
18,000
42,000
Indoor unit 2
Indoor unit 1
Connectable indoor
Total
Capacity
capacity
(Btu/h)
(Btu/h)
60,000
60,000
30,000
24,000
72,000
18,000
Indoor unit 1
Indoor unit 2
Connectable indoor
Total
Capacity
capacity
(Btu/h)
(Btu/h)
60,000
60,000
36,000
36,000
108,000
36,000
- (06 - 02) -
Capacity ratio
70%
unit capacity
Min.
Max.
50%
130%
30,000 < 42,000 < 78,000 →
30,000
78,000
Indoor unit 3
unit capacity
Min.
Max.
50%
130%
30,000 < 72,000 < 78,000 →
30,000
78,000
Indoor unit 3
unit capacity
Min.
Max.
50%
130%
30,000
78,000
Judgement
≤
≤
OK
Capacity ratio
120%
Judgement
≤
≤
OK
Capacity ratio
180%
Judgement
≤
78,000 < 108,000 →
Prohibited