Fujitsu Airstage J-II Series Design & Technical Manual page 772

Small vrf system
Table of Contents

Advertisement

2-14. WIRED REMOTE CONTROLLER (Touch panel)
2-14-1. REMOTE CONTROLLER ADDRESS SETTING
„ CONFIRM THE REMOTE CONTROLLER ADDRESS
1) When the [RC Address Setting] on the
"Maintenance" screen is touched, the
"Installer Password Verification" screen
is displayed.
Maintenance
Test Run
I.U. Address
Verification
Back
NOTE:
The address of this unit is set automatically. Do not change the indoor unit remote controller address from the
factory setting "0". (Verify that the address is "0".)
„ IF MANUALLY SETTING THE REMOTE CONTROLLER ADDRESS
1) Touch the [Manual Addressing] on the
"R.C.Address Setting" screen.
R.C.Address Setting
Current Address
Manual Addressing
Address Reset
3) When the [Yes] on the verification
screen is touched, a message screen
is displayed.
Manual Addressing
Manual address setting will be started. OK?
No
NOTES:
● Perform manual address setting only when setting the address with an arbitrary number. Indoor unit remote
controller address setting is necessary. Set the remote controller address of indoor units connected by the same
remote controller cable within a range of 1 to 9 and A (10) to F(15) so that there is no duplication. (Do not set to
"0".)
● The address of this unit is set within a range of 1 to 32, but set it so that it does not duplicate the remote
controller address of an indoor unit connected by the same remote controller cable.
Page 2/ 3
R.C. Address
Setting
Function Setting
Previous
Next
Page
Page
[001–01]
Back
Yes
- (07 - 125) -
2) Enter the Installer Password, and touch the [OK].
"R.C.Address Setting" screen is displayed.
The address of this unit is displayed on the
"R.C.Address Setting" screen.
R.C.Address Setting
Current Address
[001–01]
Manual Addressing
Address Reset
Back
When the [Back] is touched, the display returns to
the "Maintenance" screen.
2) "Manual Addressing" screen is displayed. Set
the address with [▲] or [▼].
Manual Addressing
System
Unit
001
01
Cancel
When the [OK] is touched, a verification screen is
displayed.
4) When the [Close] on the message screen is
touched, the display returns to the "R.C.Address
Setting" screen. Turn on the power again.
Manual Addressing
Setting is reflected after the power is
turned on again.
Close
R.C.address
(Unit No.)
When the address
is set manually, this
mark is displayed.
OK