INSTALLATION MANUAL INDOOR UNIT (Duct type) For authorized service personnel only. MANUEL D’INSTALLATION APPAREIL INTÉRIEUR (type conduit) Pour le personnel agréé uniquement. MANUAL DE INSTALACIÓN UNIDAD INTERIOR (Tipo conducto) Únicamente para personal de servicio autorizado. ARUL7TLAV ARUL9TLAV ARUL12TLAV ARUL14TLAV ARUL18TLAV PART NO.
INSTALLATION MANUAL • Hazard alerting symbols PART NO. 9374342358-03 VRF system indoor unit (Duct type) Electrical Contents SAFETY PRECAUTIONS ..................1 Safety/alert 1.1. IMPORTANT! Please read before starting ............1 1.2. SPECIAL PRECAUTIONS ................. 1 ABOUT THIS PRODUCT..................2 If Necessary, Get Help 2.1.
Do not turn ON the power until all work has been completed. Name and Shape Q’ty Application Turning ON the power before the work is completed can cause serious accidents such as electric shock or fi re. Operating Manual If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a fl...
1 (20) or more 2.5. About unit of the length All Fujitsu General products are manufactured to metric units and tolerances. United States customary units are provided for reference only. In cases where exact dimensions and tolerances are required, always refer to metric units.
screw Right side Cover (PIPE side) Duct Grille Left side Inlet air 6 (150) 6 (150) Fan guard or more or more Strong and durable fl oor Strong and 16 (400) 1 (20) 1 (20) 6 (150) durable fl oor or more or more or more...
Hanger bolt AR7/9/12/14 AR18 25-9/16 (650) 33-7/16 (850) Hanger Nut A P 7-7/8 (200) × 2 = 15-3/4 (400) P 7-7/8 (200) × 3 = 23-5/8 (600) (Field supply) Washer 3.3A.2. INSTALL THE FILTERS (Accessories) Unit • Install the fi lters to the unit. Nut B (Field supply) 13/16...
Page 7
3.3B.1. UNIT INSTALLATION EXAMPLE (Wall mounted type/Floor standing concealed type) Connect the locally purchased duct. Unit Filter (1) Inlet side • Connect the duct to the locally purchased inlet fl ange. • Connect the fl ange to the body with the locally purchased tapping screws. •...
4.3.1. Flaring 4. PIPE INSTALLATION Use special fl are tool exclusive for R410A. Cut the connection pipe to the necessary length with a pipe cutter. CAUTION Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
Tighten with 2 wrenches. 5.1A. When drain pump is used Holding wrench • Use general hard polyvinyl chloride pipe ø 3/4 in. (19 mm) [I.D.], ø 1-1/16 in.(27 mm) [O.D.] . • Do not perform a rise, trap and air bleeding. Flare nut Torque wrench •...
(1) Ceiling concealed type 5.2. Install the drain pipe Gap of 60 to 78 in. (1.5 to 2 m) (1) Be sure to use supplied Drain hose 1 and Hose band 2 GOOD Downward gradient 2 Hose band (Accessories) 0.10 to 0.19 in. (2.5 to 5.0 mm) 1 Drain hose (Accessories) Supporter...
• STEP1 - STEP3 CAUTION Butt the insulation against the unit. Make sure the drain water is properly drained. Unit 6. ELECTRICAL WIRING Slit WARNING Electrical work must be performed in accordance with this Manual by a person certifi ed under the national or regional regulations.
Breaker shall be located in sight from and readily accessible from all indoor units. 6.1. Electrical requirement *1: When connecting to the Heat Recovery System, refer to the installation manual of the RB unit. Voltage rating 208 / 230 V *2: When connecting the 2-wire type remote controller, Y3 is not used.
Strip 3/8 in. Ring terminal 6.4. Connection of wiring (10 mm) (1) Remove the cover. (2) Connect the connection cable. Sleeve Cover Screw with spe- Screw with cial washer special washer Cable Ring terminal Screw Ring terminal Terminal block Cable WARNING CAUTION Use ring terminals and tighten the terminal screws to the specifi...
6.5. External input and external output (Optional DC power supply P.C.B 12 to 24V parts) Load resistance CNA01 CAUTION Do not operate any switches other than prescribed, as it can cause the unit to operate P.C.B improperly or malfunction. Load resistance Use an insulated screwdriver to set the DIP switches.
Page 15
[In the case of “Pulse” input] ● When connecting with unit equipped with a power supply P.C.B Connector Input signal Command Connected OFF → ON Operation device 1 CNA01 or CNA02 OFF → ON Stop Connected device 2 * The last command has priority. Connected device 3 * The indoor units within the same remote controller group operates in the same mode.
(1) Indoor unit address 6.9. Optional parts cable binding Rotary switch (IU AD × 1)...Factory setting “0” Rotary switch (IU AD × 10)...Factory setting “0” When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD SW as shown in the Table A. (2) Refrigerant circuit address Rotary switch (REF AD ×...
7.2. Custom code setting 7.4. Switching of drainage function Selecting the custom code prevents the indoor unit mix-up. If contained drain pump is not used, set the drainage function to “Invalid” in the drainage (Up to 4 codes can be set.) function switching.
Function 7.6. Function setting Function Setting number Default Details number Auxiliary • FUNCTION SETTING can be performed with the wired or wireless remote controller. ○ heater (The remote controller is optional equipment) control 1 • Refer to the wired or wireless remote controller manual for detailed setting information. Auxiliary (Set IU AD, REF AD SW to 0) heater...
10. ERROR CODES 9. CHECK LIST If you use a wired type remote controller, error codes will appear on the remote control- Pay special attention to the check items below when installing the indoor unit(s). After ler display. If you use a wireless remote controller, the lamp on the photodetector unit installation is complete, be sure to check the following check items again.