Fujitsu Airstage J-II Series Design & Technical Manual page 651

Small vrf system
Table of Contents

Advertisement

„ KINDS OF ADDRESS AND SETTING RANGE
UNIT
SETTING
Refrigerant
O
circuit address
RB unit
P RB unit address
Touch panel
G
Controller /
controller
Convertor
address
Network
H
convertor
Refrigerant
circuit address
Dual remote
Wired remote
I
control
controller
Dual remote
Simple remote
I
control
controller
Signal
Signal amplifier
K
amplifier
address
Modbus
®
Q
convertor
Network
Controller /
convertor for
M
Convertor
L
W
address
ORKS ®
ON
Central
remote
N
controller
Remote
F
controller
Wired remote
address
controller
(Touch panel)
Dual remote
J
control
*Set up after confirming the details of each unit.
*1: The sum total of the Touch panel controller, Central remote controller and Network convertor for L
maximum of 16.
NOTE: Address of the Touch panel controller, Central remote controller, Modbus
for LONWORKS® must not be same.
*2: The address can be set from 1 to 32. However, do not set the same number as that for the remote-controller
address of an indoor unit connected using the same remote-control cable.
Set "Remote controller address" of Wired remote controller (Touch panel) in Manual address setting only. It is not
necessary to set in Automatic address setting.
SETTING
TYPE OF SWITCH
RANGE
n Manual address setting
Setting
00 ~ 99
example
01
n Automatic address setting
Set this switch to 00 at factory setting.
n Manual address setting
Setting
00 ~ 63
example
12
n Automatic address setting
Set this switch to 00 at factory setting.
00 ~ 15
*1
Setting
example
00 ~ 99
01
ON/OFF
SW 2 of DIP Switch 1
ON/OFF
SW 2 of DIP Switch 1
n Manual address setting
1 ~ 8
n Automatic address setting
Set to 1 at factory setting.
00 ~ 15
*1
1 ~ 32
n Manual address setting
*2
0 ~ 15
n Automatic address setting
ON/OFF
- (07 - 04) -
Arbitrary numbers can be
See the setting method 2-9.
REF AD
REF AD
x10
x1
See the setting method 1-5-3.
Arbitrary numbers can be
See the setting method 2-9
RB AD
RB AD
x10
x1
See the setting method 1-5-3.
See the setting method 2-14.
See the setting method 2-16.
SW 110
SW 111
(10 digit) (1 digit)
See the setting method 2-10.
See the setting method 2-11.
See the setting method 2-17.
See the setting method 1-5-1
See the setting method 2-18.
See the setting method 2-19.
See the setting method 2-13.
See the setting method 2-14-1.
See the setting method 2-14-2.
®
convertor and Network convertor
REMARKS
set in range of 00-99.
set in range of 00-63.
and 2-15.
®
W
is a
ON
ORKS