z RC AD setting
●Remote controller address switch
When the indoor unit is wired by remote controller group, to identity the indoor unit in the
remote controller group, the number (remote controller address) in the remote controller group
is set.
i) 3 wire type
Only for manual address setting
Set the remote controller address in the 0.1.2,~,15 order (Blank is not allowed)
REMOTE CONTROLLER ADDRESS SWITCH (Factory setting : 0)
Rotary SW
RC AD
ii) 2 wire type
It can choose either automatic address setting or manual address setting.
 When setting the automatic address.
Set the remote controller address in the "0" only. (Factory setting is "0")
 When setting the manual address.
Set the remote controller address in the 1.2,~,15
REMOTE CONTROLLER ADDRESS SWITCH (Factory setting : 0)
Rotary SW
RC AD
NOTE: When setting the manual address, cannot be set the "0".
Description
Remote controller address
Description
Remote controller address
- (07 - 88) -
Remarks
Remote controller address
Remarks
Remote controller address