Fujitsu Airstage J-II Series Design & Technical Manual page 877

Small vrf system
Table of Contents

Advertisement

1-5-4. CONTROLLER EXTERNAL INPUT / OUTPUT FUNCTION
SUMMARY
„ CONTROLLER EXTERNAL INPUT FUNCTION
Dry
Central
contact /
controller
Apply
(Input function)
voltage
Dry
contact
(Screen icon)
Touch
Panel
Controller
Apply
voltage
(Screen icon)
Dry
contact
(Screen icon)
Central
Remote
Controller
Apply
voltage
(Screen icon)
*1 : Default setting is Edge signal, if you use pulse signal, must be set pulse signal from screen icon.
„ CONTROLLER EXTERNAL OUTPUT FUNCTION
Dry
Central Controller
contact /
(Output Function)
Apply
voltage
Touch
Apply
Panel
voltage
Controller
Central
Apply
Remote
voltage
Controller
Function
Emergency
Batch on /
stop
Batch off
(Screen icon)
(Screen icon)
(Screen icon)
(Screen icon)
Function
Operation
Error
status
status
-
-
Signal
Terminal
type
TM201 (CH1-K1,K2)
Edge
[CN201 ↔ CN411]
TM201 (CH1-K1,K2)
(CH2-K1,K2)
Pulse *1
[CN201 ↔ CN411]
TM201 (CH1-K1,K2)
Edge
[CN201 ↔ CN412]
TM201 (CH1-K1,K2)
(CH2-K1,K2)
Pulse *1
[CN201 ↔ CN412]
CN6 (PIN1-2)
Edge
CN6 (Ch1:PIN1-2)
Pulse *1
CN7 (Ch2:PIN1-2)
CN11 (PIN1-3)
Edge
CN11 (Ch1:PIN1-3)
Pulse *1
CN12 (Ch2:PIN1-3)
Terminal
CN410
-
(PIN1-2)
CN410
(PIN3-4)
CN9
-
(PIN3-4)
CN9
(PIN1-2)
- (08 - 57) -
Specifications
External power supply
Allowable
Allowable
voltage
current
-
-
10 mA or
DC 12 [V]
less
-
-
5 mA or
DC 24 [V]
less
Specifications
External power supply
Allowable
Allowable
voltage
current
15 mA
DC 12 [V]
or less
Wire
size /
length
AWG22
Twist /
82 ft.
(25 m)
Wire
size/ length
AWG22
Twist /
Max.
82 ft.
(25 m)