Fujitsu Airstage J-II Series Design & Technical Manual page 527

Small vrf system
Table of Contents

Advertisement

 When performing periodical settings like schedule settings for the following functions, perform the setting to all the
indoor units in the same refrigerant system simultaneously, conforming to the timing restriction described below.
<Corresponding function>
· Start operation
· Release indoor unit forced
thermostat off mode
 Forced thermostat OFF instruction, outdoor unit forced off instruction and capacity save setting.
 Only one equipment can send these instructions for each refrigerant system.
 When these instructions are sent by multiple equipment (eg.from System Controller & BACnet
same time), the system may not respond as instructed or may malfunction.
 The electricity charge apportionment function of VRF system can only be performed from one equipment simultaneously.
Therefore, ECA setting, required to be set before performing electricity charge apportionment, can only be sent from one
equipment simultaneously.
 The energy saving function of VRF system can only be performed from one equipment simultaneously. Therefore, ES
setting, required to be set before performing energy saving, can only be sent from one equipment simultaneously.
„ PACKING LIST
Name and shape
WHITE-USB-KEY
(software
protection key with software)
„ OTHER REQUIRED DEVICES (Locally purchased)
● Personal computer that satisfies the following system requirements
● Echelon
U10 USB Network Interface – TP/FT-10 Channel (Model number: 75010R) (Required
®
for each VRF Network.)
„ PERSONAL COMPUTER SYSTEM REQUIREMENTS
• Microsoft
• Microsoft
• Microsoft
• Microsoft
Operating system
• Microsoft
• Microsoft
[Supported languages]
English, Chinese, French, German, Russian, Spanish, and Polish
®
CPU
Intel
Memory
• 2 GB or more (for Windows
• 4 GB or more (for Windows
HDD
40 GB or more of free space
Display
1,024 × 768 or higher resolution
• Ethernet port (for getting access to the Internet using LAN)
• USB ports (Maximum of 5 ports)
Interface
- 1 USB port is required for WHITE USB-Key connection
- Maximum of 4 USB ports are required for Echelon
* Maximum number of required USB ports depends on the applicable system configurations.
Software
Adobe
More than 10 minutes must elapse
More than 10 minutes must elapse
Quantity
Includes the software and manuals for Web Monitoring Tool.
Additionally, it works as the software protection key.
1
Software protection key to be connected to an USB port on the PC
that the Web Monitoring Tool is installed. Web Monitoring Tool runs
only on a PC with this WHITE-USB-KEY.
®
®
Windows
7 Home Premium (32-bit or 64-bit) SP1
®
Windows
®
7 Professional (32-bit or 64-bit) SP1
®
®
Windows
8.1 (32-bit or 64-bit)
®
Windows
®
8.1 Pro (32-bit or 64-bit)
®
®
Windows
10 Home (32-bit or 64-bit)
®
Windows
®
10 Pro (32-bit or 64-bit)
TM
Core
i3 2 GHz or higher
®
7 [32-bit])
®
7 [64-bit], Windows
®
®
Reader
9.0 or later
- (05 - 164) -
· Stop operation
· Set indoor unit forced thermostat
off mode
Application
®
®
8.1, and Windows