Fujitsu Airstage J-II Series Design & Technical Manual page 599

Small vrf system
Table of Contents

Advertisement

(4) Connecting pipe locally purchased from outdoor unit, cut the pipe end to connect the pipe
and close the opposite end.
Cut 1 in. (25mm)
Liquid pipe
(5) Use header support as necessary.
Ceiling
Pedestal
(Procure locally)
z Restriction when install
Be sure following restriction.
1) Installation angle
Install the header so that it branches horizontally.
Gas pipe
Horizontal
Liquid pipe
Horizontal
OK
Use a level to make sure that the header is positioned as shown in following figure, and then,
secure it in place.
Gas pipe
Outdoor
A
unit side
Brazing
point
Liquid pipe
Outdoor
B
unit side
Brazing
point
Field piping
Pipe cutter
Gas pipe
Hanging metal
(Locally purchased)
Prohibited
Horizontal
line
View from A
H 1 1
Vertical
line
Horizontal
line
2
H 2
View from B
- (06 - 35) -
Ceiling
Liquid pipe
Prohibited
H1=0 in. (0 mm) to 3/8 in. (10 mm)
1
Horizontal
(α1 : 0° to 1°)
line
β1 : -10° to +10°
H2=0 in. (0 mm) to 3/8 in. (10 mm)
(α2 : 0° to 1°)
β2 : -10° to +10°
2
Hanging metal
(Locally
purchased)