Fujitsu Airstage J-II Series Design & Technical Manual page 587

Small vrf system
Table of Contents

Advertisement

z Selection of pipe size
a
Liquid pipe
3/8"
1/4" (6.35)
(9.52)
in. (m)
Gas pipe
3/4"
(19.05)
(12.70)
in. (m)
Length ft. (m)
131 (40)
49 (15)
Example
f
Liquid pipe
3/8"
1/4" (6.35)
(9.52)
in. (m)
Gas pipe
5/8"
(15.88)
(12.70)
in. (m)
Length ft. (m)
16 (5)
32 (10)
Example
z Limitation check
Total pipe length
Between outdoor unit and farthest indoor unit
Between the first separation tube and the farthest indoor unit
Between outdoor unit and the nearest indoor unit
Between outdoor unit and the first separation tube
z Calculation of additional charge refrigerant
1. Calculation of additional amount for pipe length
Liquid pipe size
in. (m)
Additional refrigerant
lbs./ft. (kg/m)
Liquid pipe length
ft. (m)
A = (0.039 x 230) + (0.014 x 270) = 12.75 (lbs.)
[(0.058 x 70) + (0.021 x 82) = 5.79 (kg)]
2. Factory charged amount
Outdoor unit
B = 11.7 (lbs.)
[5.30 (kg)]
3. Total refrigerant amount check
C = A + B = 12.75 + 11.7 = 24.45(lbs.) < 34.61 (lbs.) → OK
[5.79 + 5.30 = 11.09(kg) < 15.70 (kg) → OK]
Check pipe length and height difference between units by comparing with items shown in "2-2.PIPING
LIMITATION".
a1
b
b1
3/8"
1/4" (6.35)
(9.52)
1/2"
3/4"
1/2"
(19.05)
(12.70)
16 (5)
32 (10)
f1
g
g1
3/8"
1/4" (6.35) 1/4" (6.35)
(9.52)
1/2"
5/8"
1/2"
(15.88)
(12.70)
16 (5)
32 (10)
3/8"
1/4"
(9.52)
(6.35)
0.039
0.014
(0.058)
(0.021)
230 (70)
270 (82)
Factory charged
Model
amount lbs. (kg)
AOU60
11.7 (5.30)
c
c1
d
3/8"
3/8"
1/4" (6.35)
(9.52)
(9.52)
3/4"
1/2"
5/8"
(19.05)
(12.70)
(15.88)
16 (5)
32 (10)
16 (5)
h
1/2"
(12.70)
22 (7)
Diagram
Total
a+b+c+d+e+f+g+h
b+c+d+e+f+g+h
a+a1
a
- (06 - 23) -
d1
e
3/8"
1/4" (6.35)
1/4" (6.35)
(9.52)
1/2"
5/8"
(12.70)
(15.88)
32 (10)
16 (5)
Example
Limitation
ft. (m)
ft. (m)
498 (152) 590 (180) or less
252 (77)
393 (120) or less
121 (37)
131 (40) or less
180 (55)
16 (5) or more
131 (40)
9 (3) or more
e1
1/2"
(12.70)
32 (10)
Judge
OK
OK
OK
OK
OK

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage aou36rlavmAirstage aou48rlavmAirstage aou60rlavmAirstage auua4tlav1Airstage auua7tlavAirstage auua9tlav ... Show all

Table of Contents