3) Turn on the power to the indoor unit.
● By turning on the power indoor units initializes EEV, so make sure the piping air-tight test and
vacuuming have been conducted before turning on the power.
● Also check again to make sure no wiring mistakes were made before turning on the power.
Breaker ON
SWITCHING SELECTION OF ADDRESS SETTING MODE
4) With "Monitor Mode" screen displayed, press and hold the SET TEMP. " " button and FAN
" " button simultaneously for at least 2 seconds.
5) The Menu 1 screen is displayed. Press and hold the FAN " " button for at least 2 seconds.
Setting mode selection screen is displayed.
6) Press the SET TEMP. " " or SET TEMP. " " button to select F1 (Menu 2-F1) settings mode
or F2 (Menu 2-F2) settings mode.
F1: Initial settings mode F2: Maintenance settings mode
7) Press the "
" button. Setting item selection screen is displayed. (Item No. is displayed.)
8) Select the item number to be set with the SET TEMP. " " or SET TEMP. " " button, and
press the "
" button to switch to thesetting screen.