1-5. CENTRAL REMOTE CONTROLLER
External input
Control input
-
-
1-5-1. EXTERNAL INPUT
● This function performs "Emergency stop" or "All On / All Off" by using the signal to be input externally at external
input terminals.
„ INPUT SELECT
There are 2 kinds of input method of External input terminal: "Dry contact" or "Apply voltage
contact".
z Dry contact
When a power supply is unnecessary at the input device you want to connect, connect to CN6
and CN7.
*1
Connected unit
*1 : Short circuit detection resistance (R
Open circuit detection resistance (R
* A twisted pair cable(22AWG) should be used. Maximum length of cable is 82 ft. (25 m)
External output
Input select
Dry contact
-
Apply voltage
Operation status
Error status
PCB
) : ≤ 500 (ohm).
ON
) : ≥ 100 (kilo-ohm).
OFF
- (08 - 53) -
Connector
CN6 (and CN7)
CN11 (and CN12)
-
CN9
CN7
(Green)
CN6
(White)
External connect kit
(Optional parts)
UTY-XWZXZ7
UTY-XWZXZ8
UTY-XWZXZA