3-3. SEPARATION TUBE
„ INSTALLATION
z Separation tube
Separation tube
UTP-AX090A
z Installation
Select the connections with the pipe diameters that match the selected pipe sizes from the
separation tubes, and cut them with a pipe cutter.
Joint pipe (Separation tube)
NOTE: Insert the field pipe firmly until it touches the joint pipe (Separation tube).
When the pipe size of the separation tube itself does not match, or when piping sizes differ
even if it cuts the pipe, use attached Reducer or attached Expander.
Reducer or
Joint pipe
Expander
(Separation tube)
Field pipe
Field pipe
- (06 - 31) -
L
0 to 1/8 in. (0 to 3 mm)
1/2L
Standard cutting position:
+1/8
+3
1/2L
in. (1/2L
mm)
-0
-0