• When regularly making the following settings to the same outdoor unit by using schedule function etc., leave the
following interval.
<Corresponding function>
·Reset outdoor unit forced off mode
 When performing periodical settings like schedule settings for the following functions, perform the setting to all the
indoor units in the same refrigerant system simultaneously, conforming to the timing restriction described below.
<Corresponding function>
· Start operation
· Release indoor unit forced
thermostat off mode
 Forced thermostat OFF instruction, outdoor unit forced off instruction and capacity save setting.
 Only one equipment can send these instructions for each refrigerant system.
 When these instructions are sent by multiple equipment (eg.from System Controller & BACnet Gateway at the
same time), the system may not respond as instructed or may malfunction.
 The electricity charge apportionment function of VRF system can only be performed from one equipment simultaneously.
Therefore, ECA setting, required to be set before performing electricity charge apportionment, can only be sent from one
equipment simultaneously.
 The energy saving function of VRF system can only be performed from one equipment simultaneously. Therefore, ES
setting, required to be set before performing energy saving, can only be sent from one equipment simultaneously.
„ PACKING LIST
Name and shape
DVD-ROM
Wibu key
(Software protection key)
„ OTHER REQUIRED DEVICES (LOCALLY PURCHASED)
● Personal computer that satisfies the following system requirements
®
● Echelon
U10 USB Network Interface – TP/FT-10 Channel (Model number: 75010R) (Required
for each VRF Network.)
More than 6 minutes must elapse
More than 3 minutes must elapse
More than 10 minutes must elapse
More than 10 minutes must elapse
Quantity
Includes the software and manuals for
1
Software protection key to be inserted in a USB slot running
.
1
Gateway
BACnet
- (05 - 169) -
· Set outdoor unit forced off mode
· Stop operation
· Set indoor unit forced thermostat
off mode
Application
BACnet
may only run on a PC with Wibu Key.
®
Gateway
®
.
Gateway
®
BACnet