Step 5 Remove the four bolts from both ends of the electric heater and take out the electric heater
and its cable.
Figure 6-32 Electric heater position
Step 6 Install and secure the new electric heater by performing
maintenance baffle and close the front door.
Step 7 Power on the device. Tap Start on the home screen, and choose Maint > Diagnostic Mode >
Enter. Then start the electric heater and check that the heater operates properly. Then exit
from the diagnostic mode.
Step 8 On the home screen, choose Maint > Performance Maint to enter the performance
maintenance screen and clear the runtime of the electric heater.
----End

6.7.10.2 Replacing the Electric Heater (Downflow)

Step 1 Tap Shutdown on the display's home screen.
Exercise caution because the device is still energized when it is shut down over the display.
Step 2 Open the front door and turn off the general switch. For a device that has two power inputs,
turn off the active power switch QF1 and standby power switch QF2.
Step 3 Remove the fan maintenance baffle plate. After the electric heater cools to the room
temperature, cut off the cable tie on the electric heater cable and disconnect the
interconnection terminal.