NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Step 5 Use a flat-head screwdriver to remove the hold hoop from the condensate pipe joint of the
module 3. Pull out the condensate pipe from the module 2, and connect and secure the
condensate pipe to the module 3 using hold hoops.
Figure 3-19 Connecting the condensate drainpipe
Step 6 Pull out the fan power cable terminals X103 and X104 of module 2, connect them to the
power cable terminals of fan 3 and fan 4 respectively, and bind the power cables along the
cabling beam.
Step 7 Connect the signal cable terminal X302 of module 2 to that of module 3, and bind the power
cables along the cabling beam.
Step 8 Install the rear doors of module 2 and module 3 as well as the fan maintenance baffle plate,
and close the front doors.