NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Figure 6-21 Removing a humidifier cylinder
Step 7 Remove the sensor cable and take out the humidifier cylinder, as shown by (3)
and (4) in
Step 8 Install the new humidifier cylinder, and start the humidifier.
Step 9 Power on the NetCol5000-A and choose Maint > Diagnostic Mode on the LCD
home screen to enter the Diagnostic Mode screen. Set the value for the
humidifier to 100% and check that the humidifier runs properly. Then exit from
the diagnostic mode.
Step 10 Install the air filter and close the rear door.
----End
Follow-up Procedure
Choose Maint > Performance Maint on the home screen and then clear the
humidifier runtime.

6.5.10 Replacing the Electric Control Box

Prerequisites
Issue 15 (2020-12-10)
Figure
6-21.
A component inside the electric control box needs to be replaced.
A spare component of the same model is available and functional.