Huawei NetCol8000-C User Manual page 133

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C:
Table of Contents

Advertisement

NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Menu
Settings
(visible
for
V200R0
02
version)
T/H
sensor
(visible
for
V200R0
02
version)
Issue 06 (2020-01-13)
Parameter
Description
g function
be set to Enable, Disable, or
Enabled when active power.
Dehumidify
The dehumidifying function
ing function
can be set to Enable, Disable,
or Enabled when active
power.
Temperatur
Cold aisle, Hot aisle, Return
e and
air, or Supply air can be set as
humidity
required. The temperature and
control type
humidity set points correspond
to the selected control type can
be set.
Temperatur
This parameter controls the
e control
temperature inside the room or
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of the
humidity set point. Disable
indicates that the electric
humidifier will not be started.
Enabled when active power
indicates that the electric
humidifier will be started when
the main power is active and
the ambient humidity is lower
than the certain humidity range
of the humidity set point.
Enable indicates that the
dehumidification function will
be enabled when the ambient
humidity exceeds the certain
humidity range of the humidity
set point. Disable indicates
that the dehumidification
function will not be enabled.
Enabled when active power
indicates that the
dehumidification function will
be enabled when the main
power is active and the
ambient humidity exceeds the
certain humidity range of the
humidity set point.
When the application
scenario is cold or hot aisle
containment, you are
advised to choose Cold
aisle if the cold aisle T/H
sensors are configured, and
choose Supply air if the
cold aisle T/H sensors are
not configured.
When the application
scenario is non-aisle
containment, you are
advised to choose Return
air, and choose Cold aisle
if the cold aisle T/H sensors
are configured.
Hot aisle is not
recommended.
Average value: Select
Average value if the
125