NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
The drainpipe must have gradients (1:100 is recommended), but no trap is allowed.
The entire drainpipe should be closely wrapped with thermal insulation foam.
Figure 3-44 Connecting the upflow drainpipe
(1) Drainpipe
Figure 3-45 Connecting the downflow drainpipe
(1) Drainpipe
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
74