3.5.2.2.2 Side Pipe Routing

Context
Tools: 75# open-end wrench, 36# open-end wrench, Phillips screwdriver (used for removing
pipe clamps), 15# socket wrench (used for removing pipe hold hoops), utility knife (used for
cutting thermal insulation foam), sealant (used for pasting thermal insulation foam), screw
thread sealant
Procedure
Step 1 Cut the thermal insulation foam around the pipe hold hoop using a utility knife, and tear the
foam.
Connect pipes, wrap thermal insulation foam around the whole pipeline, and then install pipe
clamps.
Step 2 Remove the pipe clamp securing the vertical pipe using a Phillips screwdriver, as shown by (1)
in
Figure
Step 3 Remove the elbow hoops securing the horizontal pipe using a 15# socket wrench, and then
take out the bend, as shown by (2) in
Issue 06 (2020-01-13)
3-41.
Install the removed pipe clamp to the cabinet side door in
Copyright © Huawei Technologies Co., Ltd.
Step
8.
Figure
3-41.