Tools - Huawei NetCol8000-C User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C:
Table of Contents

Advertisement

NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual

3.1.2 Tools

Table
Add or delete tools as required.
Table 3-1 General tools
Name, Specifications, and Appearance
Adjustable wrench
(200 mm x 24 mm)
Socket wrench (13
mm/15 mm)
Needle-nose pliers
Measuring tape
Issue 06 (2020-01-13)
The net height of the raised floor should be greater than 400 mm for downflow units; otherwise, the
fan lowering will be affected. The raised floor is optional for upflow units.
W indicates the distance between smart cooling products, and the minimum W is 600 mm.
L indicates the front maintenance distance, and the minimum L is 900 mm. If this requirement
cannot be met, the minimum L after front doors are removed can be 800 mm.
3-1,
Table
3-2,
Table 3-3
Phillips screwdriver
(M4/M6/M8)
Pipe wrench (18#)
Diagonal pliers
Step ladder
Copyright © Huawei Technologies Co., Ltd.
and
Table 3-4
list the tools for installing the NetCol8000-C.
Flat-head
screwdriver
(M3/M4)
Electrostatic
discharge (ESD)
gloves
Combination pliers
Polyvinyl chloride
(PVC) insulation
tape
3 Installation Guide
Fixed wrench
(36#/75#)
Wire stripper
Torch
Claw hammer
32