Figure 3-1 Layout of bottom pipe routing (1)
(1) NetCol8000-C
Issue 06 (2020-01-13)
The height of raised floors is greater than 400 mm.
W indicates the distance between smart cooling products. The minimum W for upflow units is 300
mm, and the minimum W for downflow units is 500 mm.
L indicates the front maintenance distance, and the minimum L is 900 mm. If this requirement
cannot be met, the minimum L after front doors are removed can be 800 mm.