For details about how to install the direct free-cooling plenum, see the documents delivered
with it.
3.6.11 (Optional) Connecting a Differential Pressure Sensor
Bind the pressure inlet tube along the pipeline, and the distance between two binding points
should not exceed 2.5 m.
3.6.11.1 Connecting an Upflow Differential Pressure Sensor
Prerequisites
Context
After powering on the NetCol8000, choose Settings > System Settings > Common Settings,
and set Air-side difference pressure sensor type to 0~500Pa.
Procedure
Step 1 Secure the differential pressure sensor inside the cabinet using two M3 screws, with the
pressure inlet tube port facing downwards.
Issue 06 (2020-01-13)
Install either the differential pressure sensor or the cap. If the cap is installed, skip this
section.
The hoses and cables are bound along the routes.