NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
Figure 4-12 Setting SNMP port
SNMP Port is set to 161 by default.
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1.
2.
Trap Port is set to null by default.
3.
4.
Issue 06 (2020-01-13)
Tap Add under SNMP Trap.
Set Trap Address as planned and Trap Port to the actual port number.
Select the SNMP Version. If an SNMPv3 user is configured, it is recommended that
SNMP Version be set to SNMPv3.
If SNMP Version is set to SNMPv3, select an SNMPv3 user name, and then tap
as shown in
Figure
4-13.
Figure 4-13 Setting SNMP trap parameters
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
144